Interface to the User Program in the S7-200 CPU

2.3.3Status Byte (Input Register 8DI)

Meaning for the User Program

This register shows the status of the CP 243-2 relative to the AS-i master interface.

Structure of the Status Byte

Bit 7

0

Bit 6

ASI_RESP

Bit 5

0

Bit 4

0

Bit 3

0

Bit 2

0

Bit 1

CP_READY

Bit 0

ASI_MODE

Description of the Bits

Table 2-1

 

 

 

Bit

Value

 

 

ASI_MODE

0

 

 

 

1

 

 

CP_READY

0

 

 

 

1

 

 

ASI_RESP

0/1

 

 

Meaning

The CP 243-2 is in the protected mode.

The CP 243-2 is in the configuration mode.

The CP 243-2 is not yet operational after turning on the power supply. Evaluation of the I/O data or other information from the CP is not permitted.

The CP 243-2 is operational.

Response bit for the AS-i command interface (see Section 5.1).

2-10

SIMATIC NET CP 243-2 AS-i Master

C79000-G8976-C142/02

Page 36
Image 36
Siemens CP 243-2 Status Byte Input Register 8DI, Structure of the Status Byte, Description of the Bits, Bit Value