Command Interface

5.2.12Select_Autoprogramming

Purpose

This call can enable or disable the ªautomatic address programmingº function (see also Section 6.1).

The AUTO_ADDR_ENABLE bit is stored permanently; in other words it is retained after a warm/hot restart on the AS-i master.

Structure of the Job Data in the Send Buffer

Bank Byte

20

21

 

Meaning

Bit 7

Bit 1

 

Bit 0

 

 

 

 

 

Command number: 0B H

reserved

 

Value for AUTO_ADDR_ENABLE

 

 

1=Automatic address programming

 

 

enabled

 

 

0=Automatic address programming

 

 

disabled

Structure of the Job Data in the Receive Buffer

Bank Byte

20

21

Meaning

Echo of the command number: 0B H

Command status

5-24

SIMATIC NET CP 243-2 AS-i Master

C79000-G8976-C142/02

Page 92
Image 92
Siemens CP 243-2 installation instructions SelectAutoprogramming