Command Interface

5.2.9Get_Extended_Actual_Configuration

Purpose of the Command

With this call, the following configuration data of an addressed AS-i slave obtained by the AS-i master on the AS-Interface are read.

SI/O configuration

SID code

SExtended ID1 code

SExtended ID2 code

The configuration data are specified by the manufacturer of the AS-i slave. The meaning of the configuration data is described in /2/.

Structure of the Job Data in the Send Buffer

Bank Byte

20

21

Meaning

Bit 7

Bit 4

Bit 3

Bit 0

 

 

 

 

Command number 28 H

Slave address

Structure of the Job Data in the Receive Buffer

Bank Byte

2

0

 

 

2

1

 

 

22

23

 

 

Meaning

 

 

 

 

 

 

Bit 7

Bit 4

Bit 3

Bit 0

 

 

 

 

 

Echo of the command number: 28 H

 

 

 

Command status

 

 

 

 

 

ID code

 

I/O configuration

 

 

 

 

 

Extended ID1 code

 

Extended ID2 code

 

 

 

 

 

 

SIMATIC NET CP 243-2 AS-i Master

5-21

C79000-G8976-C142/02

Page 89
Image 89
Siemens CP 243-2 installation instructions GetExtendedActualConfiguration