All installations and services must be performed by qualified service personnel.

This procedure can be repeated to determine the airflow for each room in the residence. The results of these calculations are given in Table 6, below.

Table 6: Required Room Air Flowrates Based on Floor

Area for Example 2

 

Room

Room Air

Number of

Flowrate per

Room

Floor Area

Flowrate

Register

 

(Sq. Ft.)

(CFM)

Registers

(CFM)

 

 

 

 

 

 

 

Living

400

350

3

1 @ 120

2 @ 115

 

 

 

 

Dining

120

105

1

105

Kitchen

144

126

1

126

Master

360

315

2

2 @ 157

Bedroom

 

 

 

 

Bedroom

224

196

1

196

Bedroom

224

196

1

196

Master

64

56

1

56

Bathroom

 

 

 

 

Bathroom

64

56

1

56

Total

1600

1400

11

 

We will assume the airflow is approximately equally split between all registers in a particular room. This completes steps (a) through (d) of the duct sizing method.

For step (e), static pressure drops for each system, branch, and component must be selected. Since the appliance circulating blower can only tolerate a maximum pressure of 0.4 in. W.G., the combined resistance of the supply and return air systems cannot exceed this amount.