Thermo Products OPB (24, 36)- 80, 30 Proper Combustion Achieved?, Is The Problem Delayed Ignition?

Models: 30 36)- 80 OPB (24

1 91
Download 91 pages 61.55 Kb
Page 81
Image 81
PROPER COMBUSTION ACHIEVED?

All installations and services must be performed by qualified service personnel.

PROPER COMBUSTION ACHIEVED?

No

 

IS THE PROBLEM DELAYED

IGNITION?

Yes

IS THE AIR TUBE INSERTION

No

0-1/4" BACK FROM INSIDE

 

OF REFRACTORY?

 

Yes

ARE THE ELECTRODES

No

PROPERLY ALIGNED?

 

Yes

CORRECT INSERTION OR

AIR TUBE BURNOFF

MAY OCCUR.

ALIGN ELECTRODES PER BURNER INSTRUCTION MANUAL SPECIFICATIONS

Yes

No

IS PUMP PRESSURE SET

 

ACCORDING TO BURNER

No

APPLICATION CHART

 

Yes

ARE VENT TERMINAL AND HEAT

EXCHANGER CLEAN?

ADJUST TO 100-120 PSI UNLESS COMBUSTION AIR OR OIL BELOW 50 deg. F IS PRESENT (THIS

IS CONSIDERED BELOW)

IS THE NOZZLE

PLUGGING?

 

 

 

 

 

 

ADJUST AIR TO A TRACE OF

 

 

 

 

 

 

 

No

IS BURNER SET TO

No

SMOKE, THEN TAKE CO2 OR

 

 

O2 READING, NEXT SUBTRACT

 

 

 

PRODUCE A TRACE

 

 

1% FROM THE CO2 OR ADD 1%

 

 

 

OF SMOKE AND

 

 

 

 

 

TO O2 . THEN, ADJUST AIR TO

 

 

 

THEN "DETUNED".

 

 

 

 

 

OBTAIN NEW CO2 OR O2 VALUES.

 

 

 

 

 

 

Yes

IS WATER, DIRT, OR

No

SLUDGE PRESENT IN

 

IS COMBUSTION AIR

 

 

THE OIL SYSTEM?

 

 

Yes

Yes

 

 

TRY TO RAISE ROOM & OIL

REPAIR OR REPLACE TANK

IF THIS CANNOT BE DONE DO

THE FOLLOWING:

TO PREVENT FUTURE

 

PROBLEMS. MIX

 

IN PROPER ADDITIVES

DECREASE NOZZLE SIZE AND

TO REMOVE WATER

INCREASE PUMP PRESSURE.

AND SLUDGE

CHOOSE SMALLER NOZZLE

 

 

 

 

SIZE AND PUMP PRESSURE

 

 

 

 

FROM "EFFECTS OF PRESSURE

 

 

ON NOZZLE FLOW RATES" AT

 

 

THE END OF THE TROUBLE

 

 

SHOOTING SECTION.