Figure 15: Plan View of a Typical Residence

All installations and services must be performed by qualified service personnel.

Figure 15: Plan View of a Typical Residence

Solution: If certain flowrates are desired, for heating or cooling reasons, or are required, by local codes, those guidelines should be followed. In lieu of other requirements, room floor area can be used to select flowrates for each room.

For instance, the floor area of the living room is 400-sq. ft. Using the result of our previous example, the required minimum air flowrate for the residence is 1400 CFM. The air flowrate for the living room will be the total flowrate multiplied by the ratio of the living room area to the total floor area or,

400 sq. ft.

 

 

CFM Living Rm = 1400CFM *

 

= 350CFM .

 

1600 sq. ft.

 

63

Page 64
Image 64
Thermo Products 36)- 80, OPB (24, 30 service manual Plan View of a Typical Residence