I.Air Filters

All installations and services must be performed by qualified service personnel.

8.As a final step in the installation, the appliance must be adjusted to deliver a temperature rise within the range of 50° to 80°F. Adjust the blower motor speed to obtain a temperature rise within the acceptable range. The required blower speed will depend on the airflow resistance of a supply and return air duct systems.

I.Air Filters

1.Filter Installation

This OPB unit has been factory supplied with a high quality, re-usable filter rated for air velocities up to 600 ft/min.

2.Use of non-Thermo Pride Filters or Retention Means

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background : Failure to comply with minimum filter installation requirements may affect the performance and/or void the warranty on this unit.

If a method other than Thermo Pride filter racks is selected for retention of the filter and/or use of a different filter type is desired, refer to Table 4 for minimum sizing guidelines for selecting filter for the unit.

Table 4: Minimum Required Filter Area (in square inches)

 

Maximum

Model Number

Filter Type

Air Velocity

 

(ft/min)

OPB24

OPB30

OPB36

*Thermo Products

 

 

 

 

Supplied

600

192

240

288

Permanent

 

 

 

 

Standard

500

230

288

346

Permanent

 

 

 

 

Disposable

300

384

480

576

The Thermo Products supplied filter can be cut to size to fit other filter retention systems as long as the minimum size requirement is met.

NOTICE: Any internal stiffeners used in the filter must not be removed, although they can be cut to size as needed.

23