Pin

Signal name

IN

Signal/logic

Function/status

No.

/OUT

 

 

 

 

 

 

 

 

22

Communications error

OUT

Active Low

When communications cannot be achieved

 

 

 

 

between the RM-200M and the VM amplifier

 

 

 

 

or between VM amplifiers (High state when

 

 

 

 

communications are restored.)

 

 

 

 

 

23

Failure indication

OUT

Active Low

When the FAULT indicator lamp is on

 

 

 

 

 

24

Emergency broadcast

OUT

Active Low

When an Emergency broadcast is performed

 

on

 

 

by the VM amplifier or the external equipment.

 

 

 

 

(See the description of Pin 8 VM amplifier's

 

 

 

 

broadcast cutoff.)

 

 

 

 

 

25

EV-200's failure

OUT

Active Low

When the EV-200 Voice Announcement

 

 

 

 

Board fails.*1

*1 Requires installation of the optional EV-200 Voice Announcement Board.

*2 Use this pin to cut off the VM amplifier's power amplifier output to allow the "Emergency broadcast" initiated by connected external equipment to go through.

[Electrical characteristics]

Input

 

 

 

 

 

 

 

Open voltage:

3.3 V DC

Short-circuit current: Under 1 mA

Activation:

No-voltage make contact (one-shot signal is shown below.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over 100 ms

Output

 

Circuit:

Open collector (See below.)

Withstand voltage: 30 V DC

Control current:

Under 10 mA

Control current

46