Selection of installation place | Discharge direction |
In case of continued operation of the indoor unit under
Especially,
1.Unit is installed inside the ceiling with slated roof.
2.Unit is installed at a location using inside of the ceiling as fresh air
3.Kitchen
As shown in the following figure, No. of discharge directions can be selected according to the shape of rooms and installation position.
Refrigerant pipe side
If installing a unit at such place, put insulating material (glass wool, etc.) additionally on all the positions of the indoor unit which come to contact with
Set a check service opening panel at right side of the unit (size: 450 x 450mm or more) for piping, maintenance, and servicing.
Model RAV- | Possible installe ceiling height |
|
|
Up to 3.8m | |
|
|
When the height of the ceiling exceeds the distance of the item
REQUIREMENT
•To change discharge direction, use a shielding plate.
•When attaching a shielding plate, remove the ceiling panel and insert the shielding plate into the discharge port as shown in the figure below.
Shielding plate (Prepared locally)
•When using the air conditioner with
•When using the air conditioner with
Therefore, change the setting switch according to height of the ceiling.
•When using the high ceiling (1) or (2) with
WARNING
Install the air conditioner certainly to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against an earthquake.
An incomplete installation can cause accidents by the units falling and dropping.
(Unit : m)
Model | High ceiling setup | ||||||
No. of discharge direction | Set data | ||||||
|
|
|
|
|
|
|
|
Standard (at shipment) | 2.8 | 3.2 | 3.5 | 3.0 | 3.3 | 3.6 | 0000 |
|
|
|
|
|
|
|
|
High ceiling (1) | 3.2 | 3.5 | 3.8 | 3.3 | 3.5 | 3.8 | 0001 |
|
|
|
|
|
|
|
|
High ceiling (2) | 3.5 | 3.8 | — | 3.6 | 3.8 | — | 0003 |
35