Toshiba RAM-SM560BT-E, RAM-SM800KRT-E, RAM-SM560AT-E, RAM-SM800BT-E External view, Requirement

Models: RAM-SM560BT-E RAM-SM560KRT-E RAM-SM800UT-E RAM-SM800AT-E RAM-SM560UT-E RAM-SM800BT-E RAM-SM560AT-E RAM-SM800KRT-E

1 110
Download 110 pages 17.63 Kb
Page 39
Image 39

External view

REQUIREMENT

Strictly comply with the following rules to prevent damage of the indoor units and human injury.

Do not put a heavy article on the indoor unit. (Even units are packaged)

Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.

To move the indoor unit, hold the hooking metals (4 positions) only.

Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).

Carry the package by two or more persons, and do not bundle it with PP band at positions other than specified.

Ceiling bottom surface

 

 

 

 

 

 

105

 

 

 

 

 

 

Ø162

Ceiling bottom surface

Knockout square

 

 

 

 

 

 

hole for divide duct

 

 

 

 

 

 

For Ø150

 

 

 

97

120

(2 positions)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480

external dimension

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

227

 

840 Unit

254.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105

80

240

105105

840 Unit external dimension

434.5

 

 

 

130

 

 

173

 

 

 

 

 

 

 

 

 

 

 

 

113

Ø162

 

 

 

 

 

 

 

 

 

 

 

Refrigerant pipe

 

 

 

 

 

connecting port

Electric parts box

 

 

 

A

 

 

 

 

 

 

 

 

Refrigerant pipe

 

 

 

 

connecting port

 

 

 

 

 

B

 

 

 

 

 

70

 

 

 

790 Hanging bolt pitch

950 Panel external dimension

to910 Ceiling opening dimension

250

270

105

345.5

105

 

 

 

860

 

 

 

45

Take-in port of pipes

30

 

 

 

 

381.6

 

 

 

Knockout square hole

130

 

 

 

 

 

 

 

 

 

723

Hanging bolt pitch

 

 

 

for divide duct

 

 

 

 

 

 

For Ø150

210

 

 

950 Panel external dimension

 

 

 

 

 

 

 

 

 

 

 

 

860 to 910

Ceiling opening dimension

 

 

 

Hanging bolt

 

 

 

 

 

 

 

 

 

 

480

227

M10 or Ø3/8

 

 

(To be procured locally)

 

 

 

Ceiling bottom surface

120

256

35

 

97

88

Ceiling bottom

 

surface

Ceiling panel (sold separately)

Drain pipe connecting port

 

A

B

 

 

 

RAV-SM560UT-E

Ø6.4

Ø12.7

 

 

 

RAV-SM800UT-E

Ø9.5

Ø15.9

 

 

 

Considering pipe/wire connecting work inside the ceiling after the indoor unit has been hanged, select an installation place and determine piping direction.

If the ceiling has already been set before hanging the main unit, prepare refrigerant pipe, drain pipe, indoor connecting wire, remote controller cord, etc. up to the place where pipe and wire can be connected.

Check the size of the indoor unit, and match the indoor unit size, with ceiling opening size and that position using the attached installation pattern.

(Attach the pattern to the lower side of indoor unit with attached four screws M5 x 16L.)

36

Page 39
Image 39
Toshiba RAM-SM560BT-E, RAM-SM800KRT-E, RAM-SM560AT-E, RAM-SM800BT-E, RAM-SM560UT-E, RAM-SM800AT-E External view, Requirement