Toshiba RAM-SM800AT-E Refrigerant Piping, Requirement, Tightening of Connecting Part

Models: RAM-SM560BT-E RAM-SM560KRT-E RAM-SM800UT-E RAM-SM800AT-E RAM-SM560UT-E RAM-SM800BT-E RAM-SM560AT-E RAM-SM800KRT-E

1 110
Download 110 pages 17.63 Kb
Page 12
Image 12

4 REFRIGERANT PIPING

Tightening of Connecting Part

 

(Unit: N•m)

 

 

Outer dia. of copper pipe

Tightening torque

 

 

6.35mm (diam.)

14 to 18 (1.4 to 1.8kgf•m)

 

 

9.52mm (diam.)

33 to 42 (3.3 to 4.2kgf•m)

 

 

12.7mm (diam.)

50 to 62 (5.0 to 6.2kgf•m)

 

 

15.9mm (diam.)

63 to 77 (6.3 to 7.7kgf•m)

 

 

Flare at

indoor unit side

Flare at

outdoor unit side

Align the centers of the connecting pipes and tighten the flare nut strong as far as possible with your fingers.

Then fix the nut with a spanner and tighten it with torque wrench as shown in the figure.

Half union or packed valve

Flare nut

Externally

 

Internally

threaded side

 

threaded side

Fix with spanner.

Tighten with torque wrench.

As shown in the figure, be sure to use a double spanner to loosen or tighten the flare nut of the valve at gas side. If using a single spanner, the nut cannot be tightened with necessary tightening torque.

On the contrary, use a single spanner to loosen or tighten the flare nut of the valve at liquid side.

REQUIREMENT

1.Do not put the spanner on the cap. The valve may be broken.

2.If applying excessive torque, the nut may be broken according to some installation conditions.

After the installation work, be sure to check gas leak of connecting part of the pipes with nitrogen.

Cover

Pressure of R410A is higher than that of R22 (Approx. 1.6 times). Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor/outdoor units at the speci- fied tightening torque. Incomplete connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.

Do not apply refrigerating machine oil to the flared surface.

Cover

Cap

Piping valve

Loosened

Tightened

 

Flare nut

SM800 type valve at gas side

9

Page 12
Image 12
Toshiba RAM-SM800AT-E Refrigerant Piping, Requirement, Tightening of Connecting Part, SM800 type valve at gas side