•Before turning on the power supply, carry out the following procedure.
1)Using
2)Check the valve of the outdoor unit being opened fully.
•To protect the compressor at activation time, leave
Using the remote controller, operate the unit as usual.
For the procedure of the operation, refer to the attached Owner’s Manual.
A forced test run can be executed in the following procedure if the operation stops by
In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the usual operation.
NOTE
Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.
| 1, 5 |
In case of wired remote controller |
2, 4
3
UNIT
SET CL
Procedure |
| Description |
|
1 | Keep | button pushed for 4 seconds or more. [TEST] is |
|
displayed on the display part and the selection of mode in the test |
| ||
|
| ||
| mode is permitted. | TEST | |
2 | Push | button. |
|
| Using | button, select the operation mode, [COOL] or [HEAT]. |
|
3 | • Do not run the air conditioner in a mode other than [COOL] or |
| |
[HEAT]. |
|
| |
|
|
|
•The temperature controlling function does not work during test run.
•The detection of error is performed as usual.
4 | After the test run, push | button to stop a test run. | ||
(Display part is same as procedure 1. | ||||
| ||||
| Push | check button to cancel (release from) the test run mode. | ||
5 | ([TEST] disappears on the display and the status returns to a | |||
| normal.) |
|
|
47