period one
Types of Water Chillers
notes
Standard Rating Conditions
| evaporator | condenser | rating | |
chiller type | flow rate | flow rate | standard | |
|
|
|
| |
• reciprocating | 2.4 gpm/ton | 3.0 gpm/ton | ARI | |
• scroll | ||||
• | [0.043 L/s/kW] | [0.054 L/s/kW] | ||
• centrifugal |
|
|
|
|
absorption | 2.4 gpm/ton | 3.6 gpm/ton |
|
|
• |
|
| ||
[0.043 L/s/kW] | [0.065 L/s/kW] |
|
| |
|
|
| ||
• |
| 4.0 gpm/ton | ARI | |
2.4 gpm/ton | [0.072 L/s/kW] | |||
| ||||
• | [0.043 L/s/kW] |
|
|
|
4.5 gpm/ton |
|
| ||
|
|
| ||
| [0.081 L/s/kW] |
|
|
water leaving evaporator = 44°F [6.7°C] | Figure 23 | |
water entering condenser = 85°F [29.4°C] | ||
|
The standard rating conditions used for ARI certification represent a particular set of design temperatures and flow rates for which
In fact, concerns toward improved humidity control and energy efficiency have changed some of the design trends for specific applications. More commonly,
20 |