
period one
Types of Water Chillers
notes
Note: Addendum J updates the minimum IPLV efficiency requirements in the standard to match the methods included in the most current version of the ARI rating standard. At the time this booklet was printed, Addendum J had not been formally adopted as part of the standard. However, its adoption was deemed sure enough to include in this publication.
The standard requires that both full- and
Coefficient of performance (COP) is a unitless expression of efficiency, defined as useful energy out divided by energy input. A higher COP designates a higher efficiency.
3.516 kW/ton =
COP
standard
Water-Cooled Absorption Chillers
chiller type | capacity | minimum efficiency* | ||
all capacities | 0.7 | COP |
| |
|
|
|
|
|
|
|
|
| |
all capacities | 1.0 | COP | 1.05 IPLV |
all capacities
1.0 COP 1.0 IPLV
* as of October 29, 2001
Figure 28
The table in Figure 28 includes the minimum efficiency requirements for absorption water chillers. For an absorption chiller, COP is defined as evaporator cooling capacity divided by the heat energy required by the generator, excluding the electrical energy needed to operate the pumps, purge, and controls.
Again, these minimum efficiency requirements take effect on October 29, 2001. The test procedure for these chillers is ARI Standard
Section 6.3.4 of Standard 90.1 includes additional requirements for the design and operation of
24 |