period two

Chilled-Water System Design

notes

Primary-Secondary System Rules

The bypass pipe should be free of restrictions

Load terminals should use two-way modulating control valves

Figure 52

Obviously, in order to achieve variable flow at the distribution pump, the load terminals must be configured to vary the system flow. This requires the use of a modulating two-way control valve for each coil. Typically, no three-way valves or wild coils need to be used in a primary-secondary system. Their use decreases the energy savings potential from the variable-flow distribution pump. In fact, ASHRAE/IESNA Standard 90.1–1999 (Section 6.3.4.1) requires the use of modulating two-way control valves, and thus variable water flow, in most systems. Primary-secondary systems comply with this requirement.

Some systems, however, will use one three-way valve at the load terminal furthest from the distribution pump, to ensure that cold water is immediately availability to all terminals in the system.

46

TRG-TRC016-EN

Page 53
Image 53
Trane TRG-TRC016-EN manual Bypass pipe should be free of restrictions