
period three
System Variations
notes
Application Outside Range of Chiller
240gpm at 56.7°F
[15L/sat 13.7°C]
80gpm at 80°F
[5L/sat 26.7°C]
240gpm at 45°F
[15L/sat 7.2°C]
|
|
|
|
|
|
|
| °F |
|
|
|
|
|
|
| 45 | 80gpm at 45°F | ||
|
|
|
|
| at |
|
| ||
|
|
| pm |
|
| ] |
| ||
|
| g |
|
|
|
|
| ||
60 |
|
|
|
| °C | [5L/sat 7.2°C] | |||
1 |
|
|
|
| 7.2 |
| |||
|
|
|
| at |
|
|
|
| |
|
| L/s |
|
|
|
|
| ||
| 0 |
|
|
|
|
|
|
| |
[1 |
|
|
|
|
|
|
|
| |
processload
Figure 86
Application Outside the Operating Range of the Chiller
Some
Figure 86 shows a system in which the water flow requirement of the process load is below the minimum flow rate for a chiller with the required capacity. The system is designed like a primary-secondary system, but the production loop has a higher design flow rate than the distribution loop. This allows the water flow rate and ∆T through the chiller to be within the acceptable limits, while the water flow rate and ∆T through the process meet its requirements.
Alternatively, in a smaller system with a single chiller, a single pump on the chiller side of the bypass and a diverting valve to maintain the proper flow through the process load can achieve the same result.
78 |