period one

Types of Water Chillers

notes

Flow Rates and Temperatures

95°F

44°F

100°F

41°F

[35°C]

[6.7°C]

[37.8°C]

[5°C]

85°F

 

 

 

 

 

 

85°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[29.4°C]

 

 

 

 

[29.4°C]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54°F

 

 

 

 

57°F

 

 

 

[12.2°C]

 

 

 

[13.9°C]

 

 

 

 

ARI conditions

 

 

low-flow conditions

 

 

evaporator

2.4 gpm/ton

 

 

evaporator

1.5 gpm/ton

 

 

flow rate

[0.043 L/s/kW]

 

 

flow rate

[0.027 L/s/kW]

 

 

condenser

3.0 gpm/ton

 

 

condenser

2.0 gpm/ton

 

 

flow rate

[0.054 L/s/kW]

 

 

flow rate

[0.036 L/s/kW]

Figure 25

In the example system shown in Figure 25, the chilled water is cooled from 57°F [13.9°C] to 41°F [5°C] for a 16°F [8.9°C] T. This reduces the water flow rate required from 2.4 gpm/ton [0.043 L/s/kW] to 1.5 gpm/ton [0.027 L/s/kW].

Reducing water flow rates either: 1) lowers system installed costs by reducing pipe, pump, valve, and cooling tower sizes, or 2) lowers system operating costs by using smaller pumps and smaller cooling tower fans. In some cases, both installed and operating costs can be saved. Low-flow systems will be discussed in more detail in Period Three.

The two ARI rating standards mentioned previously, as well as ASHRAE/IESNA Standard 90.1–1999 (the energy standard), allow reduced chilled-water temperatures and flow rates. System design engineers should examine the use of reduced flow rates to offer value to building owners.

22

TRG-TRC016-EN

Page 29
Image 29
Trane TRG-TRC016-EN manual ARI conditions Low-flow conditions