period two
Chilled-Water System Design
notes
Excess Flow
2,000gpm at 54.6°F
[126L/sat 12.6°C]
2,000gpm at 42°F |
|
|
|
| ||
[126L/sat 5.6°C] |
|
|
|
| ||
|
|
|
|
|
| F |
|
|
|
|
| ° | |
|
|
|
|
| 2 | |
|
|
|
| 4 |
| |
|
|
|
| t |
| ] |
|
|
|
| a |
| |
|
|
| m |
| C | |
|
|
| ° | |||
|
| p |
| 6 | ||
|
| g . |
| |||
0 |
| 5 |
| |||
| t |
|
| |||
0 |
|
| a |
|
| |
2 |
|
| /s |
|
| |
|
| L |
|
|
| |
| 3 |
|
|
| ||
[1 |
|
|
|
|
1,800gpm at 42°F
[114L/sat 5.6°C]
1,800gpm at 56°F | Figure 61 | |
[114L/sat 13.3°C] | ||
|
When the flow of chilled water from the production loop exceeds the demand of the distribution loop, the direction of flow in the bypass pipe reverses. Chilled water flows from the supply side of the production loop, through the bypass pipe, and mixes with warm water returning from the distribution loop. This is called excess flow.
In this example, the pumps operating in the production loop are supplying 2,000 gpm [126 L/s] of water, while the distribution pump is pumping
1,800 gpm [114 L/s] to meet the demand of the cooling coils. The result is that 200 gpm [13 L/s] of supply water flows through the bypass pipe to be mixed with the water returning from the production loop. The temperature of the water returning to the chillers decreases to 54.6°F [12.6°C], reducing the load on the operating chillers.
Some excess flow is normal in the operation of a
If a
Some systems are designed with variable flow also in the production loop. Although this minimizes excess flow in the bypass pipe and further reduces
55 |