4532 | Mounting |
|
|
5.3Mounting on a floating roof tank
There are three methods of mounting the 4532 ATC on a floating roof tank:
•Top anchor method
•Thermo well method
•Guide wire ring method
Note! If the tank bottom has a heating coil, the clearance from the flexible tube or probe bottom hook to the tank bottom must increase according to the heating coil type.
5.3.1Top anchor method
The flexible tube is installed in a fixed pipe and stabilized by a top anchor. The 6000 Series Servo Tank Gauge and 4532 ATC can be mounted in the same fixed pipe.
| Electrical compartment | |
| Cable entry as specified | |
Top anchor | Flange | |
| ||
| Flexible tube | |
| Fixed pipe | |
Gas hole |
| |
Tensioning wire |
| |
Element position #1 | Ø26mm (1.02") | |
(Bottom element) | ||
| ||
| Clearance below | |
500mm (19.69") | bottom hook | |
| ||
| 400mm (15.75) | |
| Gauge plate |
Figure 5-8: Top anchor application
The installation procedure is the same as for mounting on a fixed roof tank using the top anchor.
Varec, Inc. | 19 |