Operation and Description of Instrument Function | Average Temperature/Water Bottom Sensor and Converter |
|
|
VH69 Ref Voltage
Item type: read and write
Default: 200
Range: 0 ~ 255
This parameter is the setpoint for the 4532 ATC power supply failure alarm. The
4532 ATC operates with a minimum 16 VDC supply voltage via the
16VDC.
8.1.8Temperature Adjustment: VH70 ~ VH79
VH70 Element Select Item type: select Range: 0 ~ 19
Allows selection of individual temperature elements for adjustment (0 = #1 element,
5= #6 element, 19 = reference 100 Ohm resistor). Detailed values and parameters of the selected element can be shown in:
•VH71 "Zero Adjust"
•VH73 "Temperature X"
•VH74 "Position X"
•VH75 "Resistance X"
•VH76 "Resistance Adj"
VH71 Zero Adjust
Item type: read and write
Default: 0
Range:
Zero adjustment of the individual element selected at VH70. This value can be adjusted when the measured temperature of the selected element has a minor offset value as compared to a precision reference thermometer.
For example: Selected element #2 indicates 25.4 °C. The reference thermometer indicates 25.2 °C. Enter
VH72 Adjust Span
Item type: read and write
Default: 1
Range: 0.8 ~ 1.2
This span adjustment applies to all installed temperature elements. This parameter is multiplied by the raw measurement for each individual element to calculate the calculated temperature for each individual element.
Note! All of displayed individual temperature values are calculated based on the following formula.
38 | Installation and Operations Manual |