Operation and Description of Instrument Function

 

 

8.1.6WB primary and Advanced temp: VH50 ~ VH59

VH53 Element Point Item type: select Default: 0

Selection: 0 ~ 15 (element #1 = 0, element #6 = 5)

Select element number for "Advanced" average calculation at VH26. Selected element position will be displayed on VH54 "Element Position" and allow modification of the volume factor at VH55 "Element Volume" for the specified element.

VH54 Element Position Item type: read only Range: 0m ~ 99999mm

A display of selected element position on VH53.

VH55 Element Volume Item type: read and write Range: 1 ~ 99999.9

For the selected element at VH53 "Element Point", extra volume can be added to the specified element for advanced average temperature calculation. (For details, refer to the description of VH26 "Select Average Method" on page 30)

8.1.7WB Adjustment and Operation Power: VH60 ~ VH69

VH67 Common Voltage Item type: read only Range: 0 ~ 255 (0 ~ 3V)

A display of temperature element line (both signal and common) running voltage. The detected voltage across the common line (between 0 ~ 3V) is converted to a range of 0 ~ 255 counts when it is displayed.

VH68 Output Current Item type: read and write Default: 16000 at 6mA Range: 0 ~ 65536

Adjustment of 4532 ATC current consumption. In order to prevent current over-shoot within the multidrop HART loop, this function limits the 4532 ATC power consumption based on the set parameter. Normally, the 4532 ATC requires 6 mA or less current. Use a tester to check the current flow in the loop. Reducing this parameter makes the 4532 ATC use less current.

Varec, Inc.

37

Page 47
Image 47