4532

Operation and Description of Instrument Function

 

 

8Operation and Description of Instrument Function

8.0.1HART Device designation

HART device code "190":

Device code for temperature measurement function in 4532 ATC only.

8.0.2Device Data

Tag Number: read and write

Default: HART

A customer specific device identification and control number (or name). Tank name, site number, or any other ID can be entered.

Assembly Number: read and write

Default: 0

Manufacture control number based on production process.

8.1Temperature measurement

8.1.1Primary values: VH00 ~ VH09

VH00 Liquid Temp Item type: read only Range: -200°C ~ 240°C

Note! Display of measured liquid phase average temperature. Liquid level input must be provided by the 7200 or 7500 Series Radar Tank Gauge (via 4590 TSM) or 6000 Series Servo Tank Gauge in order to calculate true liquid average temperature.

VH01 Gas Temp Item type: read only Range: -200°C ~ 240°C

Display of measured gas (vapor) phase average temperature.

Note! Display of measured gas (vapor) phase average temperature. Liquid level input must be provided by the 7200 or 7500 Series Radar Tank Gauge (via 4590 TSM) or 6000 Series Servo Tank Gauge in order to calculate true gas average temperature.

VH02 Measured Distance Item type: read and write Range: 0mm ~ 99999mm

Display of provided liquid level by connected level gauge. Manual level input is also available for the purpose of device testing.