4532 | Wiring |
|
|
6Wiring
6.1Terminal Connection
6.1.14532 ATC terminal
Note! The 4532 ATC allows an intrinsically safe HART connection only. Please refer to the i.s. regulation for establishing wiring and field device layout.
Z1AR1
Z2Z3
H2- H2+ H1- H1+
H2- H2+ H1- H1+
Ground terminal
Screened twisted pair |
|
or steel armored wire | to 4590 TSM |
| |
| + terminal 24, 26 or 28 |
| - terminal 25, 27 or 29 |
| or |
| to 6000 STG |
Note! | + teminal 24 |
- terminal 25 |
Metal cable gland only:
Shield of HART communication line must be grounded
Temp. data
I.S. HART on 4532 ATC
+: H1 + terminal
-: H1 - terminal
Figure 6-1: 4532 ATC terminal
The 4532 ATC has convenient daisy chain HART loop terminals that enable the 4532 ATC to be a terminal junction for HART
Varec, Inc. | 23 |