Operation and Description of Instrument Function

Average Temperature/Water Bottom Sensor and Converter

 

 

VH07 Temperature 0

Item type: read only

Display of converted 100 Ohm reference resistor deviation value compared to actual inserted element value in temperature probe. The reading value of reference resistor and its deviation are continuously monitored during operation to prevent an incorrect calculation.

VH09 Temperature 17

Item type: read only

Display of the converted 200 Ohm reference resistor deviation value compares to the actual inserted element value in the temperature probe. The reading value of the reference resistor and its deviation are continuously monitored during operation to prevent an incorrect calculation. Indicated tolerance should be within ±0.15°C (±0.27°F) depending on element characteristics.

8.1.2Element Temperature 1: VH10 ~ VH15

(VH16~19 used only in 4539 ATC539)

VH10 ~ 19 Temperature 1 ~ 10 Item type: read only

Range: -200°C ~ 240°C

Display of individual measured element temperature.

8.1.3Element Temperature 2: VH20 ~ VH29

( not available in 4532 ATC)

VH26 Selec. Ave Method Item type: select

Selection: Standard, Advanced

Selection of average calculation method.

Standard

A Conventional calculation method. Regardless of tank shape, average temperature calculation will be performed based on the following example (example: liquid temperature).

32