4532 | Troubleshooting |
|
|
10Troubleshooting
10.1 System error messages
Code | Description | Possible cause | Remedy |
1 | Common line open | Ground (common) line has open | Check connector |
|
| circuit. All temperature element | attachment on the module; |
|
| signals will be disabled or | then check continuity on |
|
| inaccurate. | common (black & white) |
|
|
| cable |
3~39 | Element open | Temperature element signal | Check connector |
|
| cable | attachment on the module; |
|
| ( #1 ~ 6) has open circuit. | then check continuity on |
|
|
| pointed signal cable (#1 ~ |
|
|
| 6) |
4~40 | Element short | Temperature element signal | Disengage connector from |
|
| cable | the module; then check |
|
| ( #1 ~ 6) has short circuit. | continuity on pointed |
|
|
| signal cable (#1 ~ 6) |
23 | #0 element over | When reference #0 element has | Check power supply |
| range | more than ±1.1°C deviation | voltage on 4532 ATC HART |
|
| from 0°C. | terminal H+ and H- |
24 | Memory defect | When a defect was discovered | Replace main CPU board |
| (ROM) | during whole memory |
|
|
| parameter check. Cyclic data |
|
|
| comparison between previous |
|
|
| check sum to current one. |
|
29 | Element exposed | Liquid level dropped below #1 | No liquid temperature |
|
| element position. | measurement is available. |
32 | Low power supply | Supply voltage on multi drop | Check power supply on the |
|
| HART loop to 4532 ATC is below | host instrument and |
|
| 16VDC from designated host | consumption of connected |
|
| instrument. | loop powered HART device |
41 | Memory defect | Fault during Write and Read | Replace main CPU board |
| (RAM) | sequence, not completed. |
|
42 | Memory defect | Fault during Write and Read | Check the write command |
| (EEROM) | sequence, not completed. | itself that is acceptable to |
|
|
| 4532 ATC; if command is |
|
|
| OK, replace main CPU |
|
|
| board |
These error codes are displayed on the ToF tool display when the ToF tool is properly connected. For details regarding the error display on host instrument, please refer to documentation of 4590 TSM or 6000 Series Servo Tank Gauge.