Constant Sweep Time Exceeded

The Fault Group Constant Sweep Time Exceeded occurs when the PLC CPU operates in CONSTANT SWEEP mode, and it detects that the sweep has exceeded the constant sweep timer. The fault extra data contains the actual time of the sweep in the first two bytes and the name of the program in the next eight bytes. The fault action for this group is Diagnostic.

Correction:

(1) Increase constant sweep time.

(2)Remove logic from application program.

Application Fault

The Fault Group Application Fault occurs when the PLC CPU detects a fault in the user program. The fault action for this group is Diagnostic, except when the error is a Subroutine Call Stack Exceeded, in which case it is Fatal.

Error Code:

7

Name:Subroutine Call Stack Exceeded

Description: Subroutine calls are limited to a depth of 8. A subroutine can call another subroutine which, in turn, can call another subroutine until 8 call levels are attained.

Correction: Modify program so that subroutine call depth does not exceed 8.

Error Code:

1B

Name:

Comm Req Not Processed Due To PLC Memory Limitations

Description:

No-wait communication requests can be placed in the queue faster than they can

 

be processed (e.g., one per sweep). In a situation like this, when the

 

communication requests build up to the point that the PLC has less than a

 

minimum amount of memory available, the communication request will be

 

faulted and not processed

Correction: Issue fewer communication requests or otherwise reduce the amount of mail being exchanged within the system.

Error Code:

5A

Name:

User Shut Down Requested

Description:

The PLC operating software (function blocks) generates this informational alarm

 

when Service Request #13 (User Shut Down) executes in the application

 

program.

Correction:

None required. Information-only alarm.

3-12

Series 90-30/20/Micro Programmable Controllers Reference Manual–September 1998

GFK-0467K