4-120 Series 90-30/20/Micro Programmable Controllers Reference Manual September 1998 GFK-0467K
4
Example:
In the following example, the offsets have been set up as described in the table below.
| _____
|%T0003 | | %Q0003
|——| |———| SER_|——————————————————————————————————————————————————————————( )—
| | |
| | BIT |
|%T0001 | |
|——|/|———|R |
| | |
|%T0002 | |
|——| |———|T |
| |_____|
| %R0100
For the sake of example, assume that the system has a 16-point discrete input in rack 0 slot 4, hasbeen executing for long enough that 572 samples (512 + 60) have been taken, and that the Enableboolean input is receiving power flow but the Reset and Trigger boolean inputs are not.Offset Register Parameter Description Value (dec) Value (hex)
0%R0100 Status: 2 0002
1 101 Status Extra Data: 1 0001
2 102 Trigger mode: 0 0000
3 103 Trigger Time Format: 0 0000
4 104 Reserved: 0 0000
5 105 Reserved: 0 0000
6 106 Reserved: 0 0000
7 107 Reserved: 0 0000
8 108 # of channels: 24 0018
9 109 # of samples to be taken: 512 0200
10 110 # of samples after trigger: 12 000C
11 111 Input module slot: 4 0004
12 112 Data Block Segment Selector: 8 0008
13 113 Data Block Offset: 200 00C8
14 114 Channel description 1:
Seg. Sel. : Length 17921 4601
15 115 Offset 0 0000
16 116 Channel description 2:
Seg. Sel. : Length -253 FF03
17 117 Offset 0 0000
18 118 Channel description 3:
Seg. Sel. : Length 3 0003
19 119 Offset 12 0012
20 120 Channel description 4:
Seg. Sel. : Length 18434 4802
21 121 Offset 8 0008