GE 90-30/20/Micro Svcreq #4 Change System Comm. Window Mode and Timer Value, High Byte Low Byte

Models: 90-30/20/Micro

1 311
Download 311 pages 52.91 Kb
Page 222
Image 222

4

SVCREQ #4: Change System Comm. Window Mode and Timer Value

Use SVCREQ function #4 to change the system communications window mode and timer value. The change will occur in the CPU sweep following the sweep in which the function is called.

Note

Of the CPUs discussed in this manual, Service Request 4 is supported only by 90-30 CPUs, beginning with Release 8.0.

The SVCREQ function #4 will pass power flow to the right unless a mode other than 0 (Limited), 1 (Constant), or 2 (Run-to-Completion) is selected.

The parameter block has a length of one word.

To disable the system communications window, enter SVCREQ function #4 with this parameter block:

High Byte

Low Byte

0

0

 

 

address

To enable the system communications window, enter SVCREQ function #4 with this parameter block:

High Byte

Low Byte

Mode

Value from 1 to 255 ms

 

 

address

GFK-0467K

Chapter 4 Series 90-30/20/Micro Instructions Set

4-141

Page 222
Image 222
GE 90-30/20/Micro manual Svcreq #4 Change System Comm. Window Mode and Timer Value, High Byte Low Byte