Example:

This example shows logic in a program block. When enabling contact OV_SWP is set, the constant sweep timer is read, the timer is increased by two milliseconds, and the new timer value is sent back to the PLC. The parameter block is in local memory at location %R3050. Because the MOVE and ADD functions require three horizontal contact positions, the example logic uses discrete internal coil %M0001 as a temporary location to hold the successful result of the first rung line. On any sweep in which OV_SWP is not set, %M0001 is turned off.

 

_____

 

_____

 

_____

 

OV_SWP

 

%M0001

—— ———MOVE_————————————————— SVC_—————————— ADD_——————————————————( )—

 

WORD

 

REQ

INT

 

 

 

 

CONST —IN

Q—%R3050

CONST —FNC

%R3051—I1

Q—%R3051

 

0003

LEN

0001

 

 

0001

 

 

 

_____

%R3050—PARM

CONST —I2

 

 

 

 

 

_____

0002 _____

 

 

_____

 

_____

 

 

 

 

M0001

 

 

 

 

—— ———MOVE_—————————————————SVC_

 

 

 

 

WORD

 

REQ

 

 

 

 

 

 

 

 

CONST —IN

Q—%R3050

CONST —FNC

 

 

 

0001

LEN

0001

 

 

 

 

0001

 

 

 

 

 

_____

%R3050—PARM

 

 

 

 

 

 

 

_____

 

 

 

4-136

Series 90-30/20/Micro Programmable Controllers Reference Manual–September 1998