B

I/O Fault Action

The fault action specifies what action the PLC CPU should take when a fault occurs. Table B-11 lists possible fault actions.

Table B-11. I/O Fault Actions

Fault Action

Action Taken by CPU

Code

 

 

 

 

 

 

Informational

Log fault in fault table.

1

 

 

 

Diagnostic

Log fault in fault table.

2

 

Set fault references.

 

 

 

 

Fatal

Log fault in fault table.

3

 

Set fault references.

 

 

Go to STOP mode.

 

 

 

 

I/O Fault Specific Data

An I/O fault table entry may contain up to 5 bytes of I/O fault specific data.

Symbolic Fault Specific Data

Table B-12 lists data that is required for block circuit configuration.

Table B-12. I/O Fault Specific Data

Decimal Number

Hex Code

Description

 

 

 

 

 

 

Circuit Configuration

 

 

 

 

1

Circuit is an input – tristate.

 

2

Circuit is an input.

 

3

Circuit is an output.

 

 

 

Fault Actions for Specific Faults

Forced/unforced circuit faults are reported as informational faults. All others are diagnostic or fatal.

The model number mismatch, I/O type mismatch and non-existent I/O module faults are reported in the PLC fault table under the System Configuration Mismatch group. They are not reported in the I/O fault table.