GE 90-30/20/Micro manual Ser, Enable Control Block

Models: 90-30/20/Micro

1 311
Download 311 pages 52.91 Kb
Page 195
Image 195

4

SER

The SER function (Sequential Event Recorder) function is used to collect data based on an event trigger. A function control block contains user-supplied information about function block execution, channel descriptions and operation parameters.

The function has a function control block, three input parameters and one output parameter, defined as follows:

Parameters:

Parameter

Description

 

 

 

 

enable

Whenever the function is enabled and the reset input is off, the SER function block will

 

collect one sample from all configured channels.

 

 

Control Block

The 78-word array begins at the Word reference you specify here, and is used to define

 

how the SER function will record data.

 

 

R

When the reset input receives power flow, the SER function will be reset regardless of

 

the state of the enable input. The function block will remain in the reset state until power

 

flow is removed from the reset input. The OK output will be turned off while in the reset

 

state. When the power flow is removed from the reset input, channel sampling will

 

resume.

 

 

T

When the trigger input receives power flow and the reset input is off, the SER moves to

 

the triggered state and records the Trigger Time, Trigger Sample Offset and a sample.

 

The trigger input requires power flow to the enable input so that a data sample may be

 

collected from all configured channels on a trigger condition.

 

The trigger sample will be recorded regardless of the number of samples taken. Once

 

triggered, the event recorder will continue sampling until the Number of Samples After

 

Trigger is satisfied. At which time it will stop collecting samples until power flow is

 

seen on the reset input

 

 

ok

The ok output is energized whenever the trigger conditions are satisfied (specified by the

 

Trigger Mode parameter), and all sampling is complete. The output will continue to

 

receive power flow regardless of the state of the enable input until the reset receives

 

power flow.

 

 

Note

This function requires version 9.00 or higher CPU firmware, and is available only on 350 and higher CPUs.

Valid Memory Types:

Parameter

flow

%I

%Q

%M

%T

%S

%G

%R

%AI

%AQ

const

none

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ok

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid reference or place where power may flow through the function.

4-114

Series 90-30/20/Micro Programmable Controllers Reference Manual–September 1998

GFK-0467K

Page 195
Image 195
GE 90-30/20/Micro manual Ser, Enable Control Block