The System Configuration Mismatch fault entry is explained below. (All data is in hexadecimal.)

Field

Value

Description

 

 

 

 

 

 

Long/Short

00

This fault contains 8 bytes of fault extra data.

 

 

 

Rack

00

Main rack (rack 0).

 

 

 

Slot

03

Slot 3.

 

 

 

Task

44

 

 

 

 

Fault Group

0B

System Configuration Mismatch fault.

 

 

 

Fault Action

03

FATAL fault.

 

 

 

Error Code

01

 

 

 

 

The following paragraphs describe each field in the fault entry. Included are tables describing the range of values each field may have.

Long/Short Indicator

This byte indicates whether the fault contains 8 bytes or 24 bytes of fault extra data.

Type

Code

Fault Extra Data

 

 

 

 

 

 

Short

00

8 bytes

 

 

 

Long

01

24 bytes

 

 

 

Spare

These six bytes are pad bytes, used to make the PLC fault table entry exactly the same length as the I/O fault table entry.

Rack

The rack number ranges from 0 to 7. Zero is the main rack, containing the PLC. Racks 1 through 7 are expansion racks, connected to the PLC through an expansion cable.

Slot

The slot number ranges from 0 to 9. The PLC CPU always occupies slot 1 in the main rack (rack 0).

Task

The task number ranges from 0 to +65,535. Sometimes the task number gives additional information for PLC engineers; typically, the task can be ignored.