SVCREQ #2: Read Window Values

Use SVCREQ function #2 to obtain the current window mode time values for the programmer communications window, the system communications window, and the background task window.

Note

Of the CPUs discussed in this manual, Service Request 2 is supported only by 90-30 CPUs, beginning with Release 8.0.

There are three modes for each window:

Mode Name

Value

Description

 

 

 

 

 

 

Limited Mode

0

The execution time of the window is limited to its respective

 

 

default value or to a value defined using SVCREQ function #3

 

 

for the programmer communications window or SVCREQ

 

 

function #4 for the systems communications window. The

 

 

window will terminate when it has no more tasks to complete.

 

 

 

Constant Mode

1

Each window will operate in a RUN TO COMPLETION mode, and

 

 

the PLC will alternate among the three windows for a time

 

 

equal to the sum of each window’s respective time value. If

 

 

one window is placed in CONSTANT mode, the remaining two

 

 

windows are automatically placed in CONSTANT mode. If the

 

 

PLC is operating in CONSTANT WINDOW mode and a

 

 

particular window’s execution time is not defined using the associated

 

 

SVCREQ function, the default time for that window is used in the

 

 

constant window time calculation.

 

 

 

Run to Completion

2

Regardless of the window time associated with a particular

Mode

 

window, whether default or defined using a service request

 

 

function, the window will run until all tasks within that window are

 

 

completed.

 

 

 

A window is disabled when the time value is zero.

The parameter block has a length of three words:

 

High Byte

Low Byte

 

 

 

Programmer Window

Mode

Value in ms

 

 

 

System Communications Window

Mode

Value in ms

Background Window

 

 

 

 

 

 

 

address

address + 1

address + 2

All parameters are output parameters. It is not necessary to enter values in the parameter block to program this function. Output values for all three windows are given in milliseconds.

GFK-0467K

Chapter 4 Series 90-30/20/Micro Instructions Set

4-137

Page 218
Image 218
GE 90-30/20/Micro manual Svcreq #2 Read Window Values, Mode Name Value Description