PID Parameter Block:

Besides the 2 input words and the 3 Manual control contacts, the PID block uses 13 of the parameters in the RefArray. These parameters must be set before calling the block. The other parameters are used by the PLC and are non-configurable. The %Ref shown in the table below is the same RefArray Address at the bottom of the PID block. The number after the plus sign is the offset in the array. For example, if the RefArray starts at %R100, the %R113 will contain the Manual Command used to set the Control Variable and the integrator in Manual mode.

Table 4-4. PID Parameters Overview

Register

Parameter

Low Bit Units

Range of Values

 

 

 

 

%Ref+0000

Loop Number

Integer

0 to 255 (for user display only)

 

 

 

 

%Ref+0001

Algorithm

N/A; set and

 

 

 

maintained by the

Non-configurable

 

 

PLC

 

%Ref+0002

Sample Period

10 milliseconds

0 (every sweep) to 65535 (10.9 Min).

 

 

 

Use at least 10 for 90-30 PLCs (see Note

 

 

 

on page 4-171).

%Ref+0003

Dead Band +

PV Counts

0 to 32000 (never negative)

 

 

 

 

%Ref+0004

Dead Band —

PV Counts

–32000 to 0 (never positive)

 

 

 

 

%Ref+0005

Proportional Gain –Kp

0.01 CV%/PV%

0 to 327.67 %/%

 

 

 

 

%Ref+0006

Derivative Gain–Kd

0.01 seconds

0 to 327.67 sec

 

 

 

 

%Ref+0007

Integral Rate–Ki

Repeat/1000 Sec

0 to 32.767 repeat/sec

 

 

 

 

%Ref+0008

CV Bias/Output Offset

CV Counts

–32000 to 32000 (add to integrator

 

 

 

output)

%Ref+0009

Upper Clamp

CV Counts

–32000 to 32000(>%Ref+10) output limit

 

 

 

 

%Ref+0010

Lower Clamp

CV Counts

–32000 to 32000(<%Ref+09) output limit

 

 

 

 

%Ref+0011

Minimum Slew Time

Second/Full

0 (none) to 32000 sec to move 32000 CV

 

 

Travel

 

 

 

 

 

%Ref+0012

Config Word

Low 5 bits used

Bit 0 to 2 for Error+/–, OutPolarity,

 

 

 

Deriv.

%Ref+0013

Manual Command

CV Counts

Tracks CV in Auto or Sets CV in Manual

 

 

 

 

%Ref+0014

Control Word

Maintained by the

PLC maintained unless set otherwise: low

 

 

PLC, unless Bit 1

bit sets Override if 1 (see description in

 

 

is set.

the “PID Parameters Details” table on

 

 

 

page 4-174)

%Ref+0015

Internal SP

N/A; set and

Non-configurable

 

 

maintained by the

 

 

 

PLC

 

 

 

 

 

%Ref+0016

Internal CV

N/A; set and

Non-configurable

 

 

maintained by the

 

 

 

PLC

 

 

 

 

 

%Ref+0017

Internal PV

N/A; set and

Non-configurable

 

 

maintained by the

 

 

 

PLC

 

 

 

 

 

%Ref+0018

Output

N/A; set and

Non-configurable

 

 

maintained by the

 

 

 

PLC

 

 

 

 

 

GFK-0467K

Chapter 4 Series 90-30/20/Micro Instructions Set

4-173

Page 254
Image 254
GE 90-30/20/Micro PID Parameter Block, PID Parameters Overview, Register Parameter Low Bit Units Range of Values, Plc