A-8Series 90-30/20/Micro Programmable Controllers Reference Manual September 1998 GFK-0467K

A
Table A-1. InstructionTiming-Continued
Function Enabled Disabled Increment Enabled Disabled Increment
Group Function 350/351/36X 350/351/36X 350/351/36X 352 352 352 Size
Data Move Move (INT) 2 0 0.41 2 0 0.41 10
Move (BIT) 28 0 4.98 28 0 4.98 13
Move (WORD) 2 0 0.41 2 0 0.41 10
Move (REAL) 24 1 0.82 24 1 0.82 13
Block Move (INT) 2 0 – 2 0 28
Block Move (WORD) 4 4 – 3 0 28
Block Move (REAL) 41 0 41 0 – 13
Block Clear 1 0 0.24 1 0 0.24 11
Shift Register (BIT) 49 0 0.23 46 0 0.23 16
Shift Register (WORD) 27 0 0.41 27 0 0.41 16
Bit Sequencer 38 22 0.02 38 22 0.02 16
COMM_REQ 765 0 765 0 – 13
Table Array Move
INT 54 0 0.97 54 0 0.97 22
DINT 54 0 0.81 54 0 0.81 22
BIT 69 0 0.36 69 0 0.36 22
BYTE 54 1 0.64 54 1 0.64 22
WORD 54 0 0.97 54 0 0.97 22
Search Equal
INT 37 0 0.62 37 0 0.62 19
DINT 41 1 1.38 41 1 1.38 22
BYTE 35 0 0.46 35 0 0.46 19
WORD 37 0 0.62 37 0 0.62 19
Search Not Equal
INT 37 0 0.62 37 0 0.62 19
DINT 38 0 2.14 38 0 2.14 22
BYTE 37 0 0.47 37 0 0.47 19
WORD 37 0 0.62 37 0 0.62 19
Search Greater Than
INT 37 0 1.52 37 0 1.52 19
DINT 39 0 2.26 39 0 2.26 22
BYTE 36 1 1.24 36 1 1.24 19
WORD 37 0 1.52 37 0 1.52 19
Search Greater Than/Equal
INT 37 0 1.48 37 0 1.48 19
DINT 39 0 2.33 39 0 2.33 22
BYTE 37 1 1.34 37 1 1.34 19
WORD 37 0 1.48 37 0 1.48 19
Notes:1. Time (in microseconds) is based on Release 7 of Logicmaster 90-30/20/Micro software for 350 and 360 Series CPUs.
2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data
move functions, microseconds/number of bits or words.
3. Enabled time for single length units of type %R, %AI, and %AQ.
4. COMMREQ time has been measured between CPU and HSC.
5. DOIO is the time to output values to discrete output module.
6. Where there is more than one possible case, the time indicated above represents the worst possible case.
7. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.