Table 2-6. System Status References - Continued

Reference

Name

Definition

%S0017

SNPXACT

SNP-X host is actively attached to the CPU.

%S0018

SNPX_RD

SNP-X host has read data from the CPU.

%S0019

SNPX_WT

SNP-X host has written data to the CPU.

%S0020

 

Set ON when a relational function using REAL data executes successfully.

 

 

It is cleared when either input is NaN (Not a Number).

 

 

 

%S0032

 

Reserved for use by the programming software.

 

 

 

 

 

 

%SA0001

PB_SUM

Set when a checksum calculated on the application program does

 

 

not match the reference checksum. If the fault was due to a

 

 

temporary failure, the discrete bit can be cleared by again storing

 

 

the program to the CPU. If the fault was due to a hard RAM

 

 

failure, the CPU must be replaced.

 

 

 

%SA0002

OV_SWP

Set when the PLC detects that the previous sweep took longer than the

 

 

time specified by the user. Cleared when the PLC detects that

 

 

the previous sweep did not take longer than the specified time. It is also

 

 

cleared during the transition from STOP to RUN mode. Only valid if the

 

 

PLC is in CONSTANT SWEEP mode.

 

 

 

%SA0003

APL_FLT

Set when an application fault occurs. Cleared when the PLC

 

 

transitions from STOP to RUN mode.

 

 

 

%SA0009

CFG_MM

Set when a configuration mismatch is detected during system

 

 

power-up or during a store of the configuration. Cleared by

 

 

powering up the PLC when no mismatches are present or during a store of

 

 

configuration that matches hardware.

 

 

 

%SA0010

HRD_CPU

Set when the diagnostics detects a problem with the CPU hardware.

 

 

Cleared by replacing the CPU module.

 

 

 

%SA0011

LOW_BAT

Set when a low battery fault occurs. Cleared by replacing the

 

 

battery and ensuring that the PLC powers up without the low

 

 

battery condition.

 

 

 

%SA0014

LOS_IOM

Set when an I/O module stops communicating with the PLC CPU. Cleared

 

 

by replacing the module and cycling power on the main rack.

 

 

 

%SA0015

LOS_SIO

Set when an option module stops communicating with the PLC

 

 

CPU. Cleared by replacing the module and cycling power on the main

 

 

rack.

 

 

 

%SA0019

ADD_IOM

Set when an I/O module is added to a rack. Cleared by cycling

 

 

power on the main rack and when the configuration matches the hardware

 

 

after a store.

 

 

 

%SA0020

ADD_SIO

Set when an option module is added to a rack. Cleared by cycling power

 

 

on the main rack and when the configuration matches the hardware after a

 

 

store.

 

 

 

%SA0027

HRD_SIO

Set when a hardware failure is detected in an option module. Cleared by

 

 

replacing the module and cycling power on the main rack.

 

 

 

%SA0031

SFT_SIO

Set when an unrecoverable software fault is detected in an option module.

 

 

Cleared by cycling power on the main rack and when the configuration

 

 

matches the hardware.

 

 

 

GFK-0467K

Chapter 2 System Operation

2-25

Page 45
Image 45
GE 90-30/20/Micro manual Reference Name Definition