4

Status Extra Data

The Status Extra Data provides additional state information for the SER function.

State

Description

Inactive State

State between the Reset State and the Active State. No actions are performed in

(1)

this state. The Boolean output is held to no power flow. Transition to the

 

Active State occurs when the function block receives enable power flow.

Active State (2)

State after the Enable Boolean input has received power flow, but the function

 

block is not reset, in error, or triggered. One sample is recorded for each

 

execution when the function block is enabled. The Boolean output is held to no

 

power flow. The Trigger condition (specified by the Trigger Mode parameter) is

 

monitored and will cause transition to the Triggered State if conditions are true.

 

If more than the “Number of Samples” have been taken then Status Extra Data

 

will be set to 0x01, otherwise it will 0x00.

Triggered State

State if the trigger condition defined by Trigger Mode is true. Additional

(3)

Samples are taken depending upon the trigger mode and parameter settings.

 

The Boolean output is held to no power flow. Transition to the Complete State

 

will occur when all sampling is complete. If more than the “Number of

 

Samples” have been taken then Status Extra Data will be set to 0x01, otherwise

 

it will be 0x00.

Complete State

State after all sampling is complete. The Boolean output receives power flow.

(4)

Only transition to the Reset State is allowed. If more than the “Number of

 

Samples” have been taken then Status Extra Data will be set to 0x01, otherwise

 

it will be 0x00.

Overrun Error

State if the Control/Data Block exceeds the end of its memory type. The

State (5)

Boolean output is held to no power flow. Only transition to the Reset State is

 

allowed. Status Extra Data has no significance and will be cleared to zero.

Parameter Error

State if there is an error in the user supplied operation parameters. The Boolean

State (6)

output is held to no power flow. Only transition to the Reset State is allowed.

 

The Status Extra Data word contains the offset into the control block at which

 

the parameter error occurred.

Status Error

State if the Status Parameter becomes invalid. The Boolean output is held to no

State (7)

power flow. Only transition to the Reset State is allowed. The invalid status

 

value will be stored in the Status Extra Data location in the Control Block.

Reset State (0)

State when the reset Boolean receives power flow. Sample Buffer, Trigger

 

Sample Offset, Trigger Time, and Current Sample Offset are all cleared to zero.

 

The Boolean output is held to no power flow. Transition to the Inactive State

 

occurs when the reset power flow is removed. Status Extra Data has no

 

significance and will be cleared to zero.

GFK-0467K

Chapter 4 Series 90-30/20/Micro Instructions Set

4-117

Page 198
Image 198
GE 90-30/20/Micro manual Status Extra Data, State Description