Fatal faults cause the PLC to enter a form of STOP mode at the end of the sweep in which the error occurred. Diagnostic faults are logged and corresponding fault contacts are set. Informational faults are simply logged in the PLC fault table.

Loss of, or Missing, Option Module

The Fault Group Loss of, or Missing Option Module occurs when a PCM, CMM, or ADC fails to respond. The failure may occur at power-up if the module is missing or during operation if the module fails to respond. The fault action for this group is Diagnostic.

Error Code:

1, 42

 

Name:

Option Module Soft Reset Failed

Description:

PLC CPU unable to re-establish communications with option module after soft

 

reset.

 

Correction:

(1)

Try soft reset a second time.

 

(2)

Replace the option module.

 

(3)

Power off the system. Verify that the PCM is seated properly in the

 

 

rack and that all cables are properly connected and seated.

 

(4)

Replace the cables.

 

 

 

Error Code:

79

 

Name:

Loss of Daughterboard

Description:

The daughterboard has been lost (i.e., not seen by the CPU) and will not function.

Correction:

Make sure the CPU has a daughterboard physically present.

 

 

Error Code:

All Others

Name:

Module Failure During Configuration

Description:

The PLC operating software generates this error when a module fails

 

during power-up or configuration store.

Correction:

Power off the system. Replace the module located in that rack and slot.

 

 

 