3 |
Error Code: | 14, 27 |
Name: | Corrupted PLC Program Memory |
Description: | The PLC operating software generates these errors when certain PLC |
| operating software problems occur. These should not occur in a |
| production system. |
Correction: | (1) Display the PLC fault table on the programmer. Contact GE Fanuc |
| PLC Field Service, giving them all the information contained in the |
| fault entry. |
| (2) Perform the corrections for corrupted memory. |
|
|
Error Code: | 27 through 4E |
Name: | PLC Operating Software Error |
Description: | The PLC operating software generates these errors when certain PLC |
| operating software problems occur. These errors should not occur in a |
| production system. |
Correction: | Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field |
| Service, giving them all the information contained in the fault entry. |
|
|
Error Code: | 4F |
Name: | Communications Failed |
Description: | The PLC operating software (service request processor) generates this |
| error when it attempts to comply with a request that requires backplane |
| communications and receives a rejected response. |
Correction: | (1) Check the bus for abnormal activity. |
| (2) Replace the intelligent option module to which the request was |
| directed. |
|
|
Error Code: | 50, 51, 53 |
Name: | System Memory Errors |
Description: | The PLC operating software generates these errors when its request for a block of |
| system memory is denied by the memory manager because no memory is |
| available or contains errors. |
Correction: | (1) Display the PLC fault table on the programmer. Contact GE Fanuc |
| PLC Field Service, giving them all the information contained in the |
| fault entry. |
| (2) Perform the corrections for corrupted memory. |
|
|
Error Code: | 52 |
Name: | Backplane Communications Failed |
Description: | The PLC operating software (service request processor) generates this |
| error when it attempts to comply with a request that requires backplane |
| communications and receives a rejected mail response. |
Correction: | (1) Check the bus for abnormal activity. |
| (2) Replace the intelligent option module to which the request was |
| directed. |
| (3) Check parallel programmer cable for proper attachment. |
|
|
Error Code: | All Others |
Name: | PLC CPU Internal System Error |
Description: | An internal system error has occurred that should not occur in a |
| production system. |
Correction: | Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field |
| Service, giving them all the information contained in the fault entry. |
|
|
Chapter 3 Fault Explanation and Correction |