GFK-0467K Chapter 3 Fault Explanation and Correction 3-9
3
Reset of, Addition of, or Extra, Option Module
The Fault Group Reset of, Addition of, or Extra Option Module occurs when an option module
(PCM, ADC, etc.) comes online, is reset, or a module is found in the rack, but none is specified in
the configuration. The fault action for this group is Diagnostic. Three bytes of fault specific data
provide additional information regarding the fault.
Correction: (1) Update the configuration file to include the module.
(2) Remove the module from the system.
This Fault Group also includes the following faults specific to systems having a daughterboard:
Error Code: 4
Name: Addition of Daughterboard
Description: There is a daughterboard present but not configured.
Correction: Make sure the configuration stored to the CPU contains the correct
daughterboard.
Error Code: 5
Name: Daughterboard Reset
Description: The daughterboard has been reset either due to the occurance of a push button
reset by the user or an internal error condition.
Correction: None