GE 90-30/20/Micro manual Location Field Meaning

Models: 90-30/20/Micro

1 311
Download 311 pages 52.91 Kb
Page 247
Image 247

4

Use the table on the following page to interpret the output values:

Location

Field

Meaning

 

 

 

Address

Function

1 = read extra status data

 

 

 

Address + 1

Error Code

An error code is placed here if the function fails because any

 

 

of the modules is not present, inappropriate, or not working.

 

 

 

Address + 2

First rack &

Rack and slot number (in the form RRSS in hexadecimal,

 

slot

where RR is the rack number and SS is the slot number) of

 

 

the first module from which the data will be read

 

 

 

Address + 3

Read data

The data read from the first module will be place here

 

from first

 

 

module

 

 

 

 

Address + 4

Second rack

Rack and slot number (in the form RRSS in hexadecimal,

 

& slot

where RR is the rack number and SS is the slot number) of

 

 

the second module from which the data will be read

 

 

 

Address + 5

Read data

The data read from the second module will be place here

 

from second

 

 

module

 

 

 

 

Address + (I * 2)

Ith rack & slot

Rack and slot number (in the form RRSS in hexadecimal,

 

 

where RR is the rack number and SS is the slot number) of

 

 

the Ith module from which the data will be read

 

 

 

Address + (I * 2) + 1

Read data

The data read from the Ith module will be place here

 

from Ith

 

 

module

 

 

 

 

Address + (N * 2)

Last rack &

Rack and slot number (in the form RRSS in hexadecimal,

 

slot

where RR is the rack number and SS is the slot number) of

 

 

the last module from which the data will be read

 

 

 

Address + (N * 2) + 1

Read data

The data read from the last module will be place here

 

from last

 

 

module

 

 

 

 

Address + (N * 2) + 2

End of list

A zero in this word indicates the end of the list of modules

 

indicator

 

 

 

 

4-166

Series 90-30/20/Micro Programmable Controllers Reference Manual–September 1998

GFK-0467K

Page 247
Image 247
GE 90-30/20/Micro manual Location Field Meaning