PLC CPU System Software Failure

Faults in the Fault Group PLC CPU System Software Failure are generated by the operating software of the Series 90-30, 90-20 or Micro PLC CPU. They occur at many different points of system operation. When a Fatal fault occurs, the PLC CPU immediately transitions into a special ERROR SWEEP mode. No activity is permitted when the PLC is in this mode. The only way to clear this condition is to cycle power on the PLC. The fault action for this group is Fatal.

Error Code:

1 through B

Name:

User Memory Could Not Be Allocated

Description:

The PLC operating software (memory manager) generates these errors when

 

software requests the memory manager to allocate or deallocate a block or blocks

 

of memory from user RAM that are not legal. These errors should not occur in a

 

production system.

Correction: Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field

Service, giving them all the information contained in the fault entry.

Error Code:

D

Name:

System Memory Unavailable

Description:

The PLC operating software (I/O Scanner) generates this error when its request

 

for a block of system memory is denied by the memory manager because no

 

memory is available from the system memory heap. It is Informational if the error

 

occurs during the execution of a DO I/O function block. It is Fatal if it occurs

 

during power-up initialization or autoconfiguration.

Correction: Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field

Service, giving them all the information contained in the fault entry.

Error Code:

E

Name:

System Memory Could Not Be Freed

Description:

The PLC operating software (I/O Scanner) generates this error when it requests

 

the memory manager to deallocate a block of system memory

 

and the deallocation fails. This error can only occur during the execution

 

of a DO I/O function block.

Correction:

(1) Display the PLC fault table on the programmer. Contact GE Fanuc

 

PLC Field Service, giving them all the information contained in the

 

fault entry.

(2)Perform the corrections for corrupted memory.

Error Code:

10

Name:

Invalid Scan Request of the I/O Scanner

Description:

The PLC operating software (I/O Scanner) generates this error when the operating

 

system or DO I/O function block scan requests neither a full nor a partial scan of

 

the I/O. This should not occur in a production system.

Correction: Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field

Service, giving them all the information contained in the fault entry.

Error Code:

13

Name:

PLC Operating Software Error

Description:

The PLC operating software generates this error when certain PLC

 

operating software problems occur. This error should not occur in a

 

production system.

Correction:

(1) Display the PLC fault table on the programmer. Contact GE Fanuc

 

PLC Field Service, giving them all the information contained in the

 

fault entry.

(2)Perform the corrections for corrupted memory.