Troubleshooting TankGate Interface
100 Installation and Operations Manual
4. Set the ID DIP Switch to the desired address (1-14). At this point, there is no further
action required by the user.
Figure 7-3: Set the ID DIP switch to the desired addresses
5. The LEDs will light (and remain steady) to indicate the address. For example, if the
ID DIP Switch is set to 1, LEDS D1 will on. If the ID DIP Switch is set to 3, LEDS D1
and D2 will be on.
Figure 7-4: Address indication from the LEDs
6. After 10 seconds, the address of the TankGate will be set to the ID DIP Switch set-
ting. The LEDS will flash for 5 seconds to indicate that the address is about to be
set.
Figure 7-5: Set the ID addresses
7. After the address is set, the TankGate will begin normal operation with a blank
database:
CPU LED: Flashing once per second
COM LED: Toggles when communicating to PC
TXD: Off when there is no database. When tank gauges are being scanned, the
TXD LED will flash
RXD: Off when there is no database. When tank gauges are being scanned, the
RXD LED will flash when a response is received.
ID = 1
ID = 1
D1
D2
D3
D4
ON
ID = 1
D1
D2
D3
D4
FLASHES