Troubleshooting | TankGate Interface |
|
|
4.Set the ID DIP Switch to the desired address
Figure 7-3: Set the ID DIP switch to the desired addresses
ID = 1
5.The LEDs will light (and remain steady) to indicate the address. For example, if the ID DIP Switch is set to 1, LEDS D1 will on. If the ID DIP Switch is set to 3, LEDS D1 and D2 will be on.
Figure 7-4: Address indication from the LEDs
D1 ON
D2
D3
D4
ID = 1
6.After 10 seconds, the address of the TankGate will be set to the ID DIP Switch set- ting. The LEDS will flash for 5 seconds to indicate that the address is about to be set.
Figure 7-5: Set the ID addresses
D1 FLASHES
D2
D3
D4
ID = 1
7.After the address is set, the TankGate will begin normal operation with a blank database:
•CPU LED: Flashing once per second
•COM LED: Toggles when communicating to PC
•TXD: Off when there is no database. When tank gauges are being scanned, the TXD LED will flash
•RXD: Off when there is no database. When tank gauges are being scanned, the RXD LED will flash when a response is received.
100 | Installation and Operations Manual |