4.15 Scaler Point (SCALER)
The Generic Scaling point allows the user to perform math functions in the TankGate. The SCALER point monitors one or more database reference values and performs an equation in the form:
Value = Ax + By + Cz + K
Note! A, B, C & K are user entered constants.
Note! x, y & z are inputs from other database points.
4.15.1Parameters
The database parameters used by the SCALER point are listed and described below:
Configuration | Function |
Parameters |
|
|
|
Tag | A Tag can contain 15 bytes of data and can include any printable ASCII |
| character. Tags can be used to identify points indicating the use of the |
| point such as “Eng Converter” . The default tag is set to “SCALER.00”. |
|
|
PntRef1 | The PntRef parameters determine the input source for the SCALER point |
PntRef2 | to monitor. Up to three references may be specified. RefValue1 is the X |
PntRef3 | term, PntRef2 is the Y term, and PntRef3 is the Z term. If a reference is |
| not specified, then it is not used in the equation. |
|
|
A | Constant that is multiplied with RefValue1 |
|
|
B | Constant that is multiplied with RefValue2 |
|
|
C | Constant that is multiplied with RefValue3 |
|
|
K | Constant K |
|
|
Deadband | Change of State deadband |
|
|
Report | Causes automatic notification to the Host (in response to a Change of |
| State Request) when the Value changes State. Parameter value can be |
| High, Low or No. Report=No disables notification. Points with Report = |
| High will be sent before points with Report = Low. The default is No. |
|
|
Maxtime | Specifies the maximum time (in secs) between automatic Change of |
| State responses being sent to the Host. Report must be set to either Low |
| or High for the Value parameter to be sent in response to a Change of |
| State Request. A value of 0 disables this option. |
| responses to be sent although the value may have not changed since |
| the last message. The default is 60. |
|
|
Dynamic Parame- | Function |
ters |
|
|
|
Value | Output value for the SCALER point. |
| Value = Ax + By + Cz + K. |
| x corresponds the RefValue1, y is RefValue2, and z is RefValue3. |
|
|
50 | Installation and Operations Manual |