8315 L&J Tankway Software Description

TankGate Interface

 

 

4.15 Scaler Point (SCALER)

The Generic Scaling point allows the user to perform math functions in the TankGate. The SCALER point monitors one or more database reference values and performs an equation in the form:

Value = Ax + By + Cz + K

Note! A, B, C & K are user entered constants.

Note! x, y & z are inputs from other database points.

4.15.1Parameters

The database parameters used by the SCALER point are listed and described below:

Configuration

Function

Parameters

 

 

 

Tag

A Tag can contain 15 bytes of data and can include any printable ASCII

 

character. Tags can be used to identify points indicating the use of the

 

point such as “Eng Converter” . The default tag is set to “SCALER.00”.

 

 

PntRef1

The PntRef parameters determine the input source for the SCALER point

PntRef2

to monitor. Up to three references may be specified. RefValue1 is the X

PntRef3

term, PntRef2 is the Y term, and PntRef3 is the Z term. If a reference is

 

not specified, then it is not used in the equation.

 

 

A

Constant that is multiplied with RefValue1

 

 

B

Constant that is multiplied with RefValue2

 

 

C

Constant that is multiplied with RefValue3

 

 

K

Constant K

 

 

Deadband

Change of State deadband

 

 

Report

Causes automatic notification to the Host (in response to a Change of

 

State Request) when the Value changes State. Parameter value can be

 

High, Low or No. Report=No disables notification. Points with Report =

 

High will be sent before points with Report = Low. The default is No.

 

 

Maxtime

Specifies the maximum time (in secs) between automatic Change of

 

State responses being sent to the Host. Report must be set to either Low

 

or High for the Value parameter to be sent in response to a Change of

 

State Request. A value of 0 disables this option. Non-zero values cause

 

responses to be sent although the value may have not changed since

 

the last message. The default is 60.

 

 

Dynamic Parame-

Function

ters

 

 

 

Value

Output value for the SCALER point.

 

Value = Ax + By + Cz + K.

 

x corresponds the RefValue1, y is RefValue2, and z is RefValue3.

 

 

50

Installation and Operations Manual

Page 60