Varec 8315 Series manual Switches and Indicators, Reset push-button SW3, Hard Reset

Models: 8315 Series

1 120
Download 120 pages 24.8 Kb
Page 20
Image 20

Hardware

TankGate Interface

 

 

there is 230 mA of field power available. At +48VDC, there is 230 mA of field power available.

Figure 2-8: Selection Jumper W3

 

 

EARTH

 

 

A B

NEUTRAL

 

 

 

LINE

 

 

 

SURGE GND

 

RS232

+

VFIELD

J7

COM1

-

 

A/TXD

 

 

RS485

B/RXD

 

VFIELD=48V

 

GND

COM1

 

 

 

RTS

 

 

 

CTS

 

 

 

TXD

 

VFIELD=24V

 

RXD

COM

 

 

0

 

 

GND

 

W3

 

+15V

AUX

 

+5V

POWER

 

GND

 

 

-15V

 

 

 

 

 

J8

2.2.2Switches and Indicators

2.2.2.1Reset push-button (SW3)

The RESET Switch is used to re-initialize the system hardware by causing it to go to a known starting state. This switch may be pressed at any time; however, it will do the following:

Re initialize System Hardware

Clear Scratch Memory

Verify Database and Re initialize if Invalid

Reset All Timers

Enable Communications

Figure 2-9: Switches SW3 on the TankGate motherboard

 

 

EARTH

 

 

A

B

NEUTRAL

 

 

 

 

LINE

 

 

 

 

SURGE GND

 

 

RS232

+

VFIELD

RESET

 

 

-

 

COM1

 

 

 

 

 

A/TXD

 

 

 

RS485

B/RXD

 

 

 

 

GND

COM1

 

 

 

 

 

 

 

RTS

 

 

 

 

CTS

 

 

 

 

TXD

 

 

 

 

RXD

COM 0 AUX

SW3

 

 

GND

 

 

+15V

 

 

+5V

POWER

 

 

 

GND

 

 

 

-15V

 

 

Hard Reset

A special form of Reset is available for occasions when the battery backed-up data base must be re initialized. This type of reset, the Hard Reset, can be performed before a database is downloaded from a host PC.

Caution! The Hard Reset should be used as a last resort if the TankGate is not functioning. A

Hard reset clears the installed database. For the Hard Reset procedure, refer to the

Troubleshooting and Maintenance chapter.

10

Installation and Operations Manual

Page 20
Image 20
Varec 8315 Series manual Switches and Indicators, Reset push-button SW3, Hard Reset