8315 L&J Tankway Software Description

TankGate Interface

 

 

 

 

 

 

 

 

 

 

Configuration Parameters

Function

 

 

 

 

 

 

Maxtime

Specifies the maximum time (in secs) between automatic Change

 

 

 

of State data being sent to the Host in response to a Change of

 

 

 

State Request. Report must be set to either Low or High for the

 

 

 

Value parameter to be sent in response to a Change of State

 

 

 

Request. A value of 0 disables this option. Non-zero values

 

 

 

cause responses to be sent even if the value has not changed

 

 

 

since the last message. The maximum is 255 seconds. The

 

 

 

default is 240.

 

 

 

 

 

 

Watchdog

Enables the watchdog task on the Motherboard. The watchdog

 

 

 

task monitors the LJ2000 point on the Model 8315 and verifies it

 

 

 

is scanning for gauges. If the Model 8215 fails, the 0x4000 and

 

 

 

the 0x0010 bits of the PntStatus will be set to indicate the failure.

 

 

 

 

 

Dynamic Parameters

Function

 

 

Level

Floating point value representing the tank level (in feet).

 

 

Temp

Floating point value representing the tank temperature (in

 

Fahrenheit).

 

 

PntStatus

Integer HEX value indicating status of point. Values are:

 

0x0002: Scan Timeout

 

0x0010: Gauge Not Responding

 

0x0020: Blown Transmit Fuse

 

0x0040: Parity Error

 

0x0080: Tankway Error

 

0x4000: Failure of the Model 8315. This bit is set if the

 

Watchdog task on the Motherboard determines that the Model

 

8315 has stopped updating.

 

 

GaugeStatus

Byte value indicating status of the gauge.

 

 

AlarmTime

Time that alarm first occurred. The point is in alarm when the

 

PntStatus is non zero.

 

 

Elapse

Time of the last scan.

 

 

ScanTime

Time of the last good reading. A reading is considered good if it

 

has no parity or time-out error, and has passed the filter criteria.

 

 

Raw1

Raw data from gauge. Value reported as hexadecimal value.

 

 

Raw2

Raw data from gauge. Value reported as hexadecimal value.

 

 

PntCheckSum

CRC-16 Checksum for point's static Configuration Parameters.

 

 

4.19.2Application

The LJ2000 point provides an interface to L&J MCG2000 Gauges. L&J Model 2000 Gauges are connected directly to a Model 8315 Tank Gauge Interface Module. The Model 8315 is automatically detected at startup, and an LJSCAN point is automatically created to manage the scanning task. The Module parameter determines which Model 8315 will be used. The ID must match the unit address of the MCG2000.

60

Installation and Operations Manual

Page 70