8315 L&J Tankway Software Description | TankGate Interface |
|
|
4.9Emulator (EMU)
The Emulator point allows the TankGate to emulate a
4.9.1Parameters
The database parameters used by the EMU point are listed and described below:
Configuration Parameters | Function |
|
|
Tag | The point description can contain 30 bytes of data and can |
| include any printable ASCII character. Descriptions can be used |
| as information relevant to any aspect of the point, such as its |
| use, location, operating information, etc. The default |
| description is set to “EMU.00”. |
|
|
LevelUnits | Specifies the engineering units for the level data. |
| F: feet, m: Millimeters |
| M: Meters |
| I: Inches |
| P: |
| The LevelUnits need to match the units specified during the |
| gauge setup. |
|
|
TempUnits | Specifies the engineering units for the temperature data. |
| TempUnitsSpecifies the engineering units for the temperature |
| data. |
| F: Fahrenheit |
| C: Celsius |
| The TempUnits needs to match the units specified during the |
| gauge setup. |
|
|
DensityUnits | Specifies the engineering units for the density data. |
| DensityUnitsSpecifies the engineering units for the density data. |
| K: kg/m3 |
| A: API |
| L=lbs/cu ft |
| The DensityUnits needs to match the units specified during the |
| gauge setup. |
|
|
PntRef1 - 50 | Input point reference for the EMU point to monitor. The PntRef |
| parameter is set to the Level parameter for the tank gauge point. |
| The temperature will be read at the same time as the level. The |
| EMU point interfaces tank gauge interface points: |
| WV1900 - |
|
|
38 | Installation and Operations Manual |