Generac 005734-0 Stopping the Engine, Automatic Idle Control, LOW OIL Pressure Shutdown System

Page 14

Operation

2.9STOPPING THE ENGINE

Shut off all loads, then unplug the electrical loads from generator panel receptacles. Never start or stop the engine with electrical devices plugged in and turned on.

Turn “Off” the Idle Control switch (if on).

Let engine run at no-load for several minutes to stabilize the internal temperatures of engine and generator.

Move Start/Run/Stop switch to “Off” position.

Close fuel valve.

2.10 AUTOMATIC IDLE CONTROL

This feature is designed to greatly improve fuel economy. When this switch is turned “On,” the engine will only run at its normal fast governed engine speed when electrical load is connected. When the load is removed, the engine will run at a reduced speed of 2100 RPM. With the switch “Off,” the engine runs at the normal fast engine speed all the time. Always have the switch OFF when starting and stopping the engine.

2.11 COLD WEATHER OPERATION/DE-ICER

Under certain weather conditions (temperatures below 40° F (4° C) and a high dew point), the engine may experience icing of the carburetor and/or the crankcase breather system. To eliminate this problem, this generator engine is fitted with a winter/summer valve. This directs hot air into the carburetor during cold weather operation. Always make sure the winter/ summer valve is in the correct location relative to the weather conditions.

2.12 LOW OIL PRESSURE SHUTDOWN SYSTEM

The engine is equipped with a low oil pressure sensor that shuts down the engine automatically when the oil pressure drops below 10 psi. If the engine shuts down by itself and the fuel tank has enough gasoline, check engine oil level.

2.12.1 INITIAL START-UP

A delay built into the low oil shutdown system allows oil pressure to build during starting. The delay allows the engine to run for about 10 seconds before sensing oil pressure.

2.12.2 SENSING LOW OIL PRESSURE

If the system senses low oil pressure during operation, the engine shuts down.

2.12.3 RESTARTING

If trying to restart the engine within 10 seconds after it shuts down, the engine may NOT start. The system needs five (5) to 10 seconds to reset.

If the engine is restarted after such a shutdown and the low oil pressure has not been corrected, the engine will run for about 10 seconds as described above and then stop.

2.13 CHARGING A BATTERY

Storage batteries give off explosive hydrogen gas while recharging. An explosive mixture will remain around the battery for a long time after it has been charged. The slightest spark can ignite the hydrogen and cause an explosion. Such an explosion can shatter the battery and cause blindness or other serious injury.

Do not permit smoking, open flame, sparks or any other source of heat around a battery. Wear protective goggles, rubber apron and rubber gloves when working around a battery. Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. If spill occurs flush area with clear water immediately.

This generator has the capability of recharging a discharged 12 Volt automotive or utility style storage battery. Do not use the unit to charge any 6 Volt batteries. Do not use the unit to crank an engine having a discharged battery.

This battery charger is a pulse type designed to provide a quality charge current into the battery. The voltage measured at the outlet should be 8-12 VDC. This is normal and does not indicate a faulty charging system.

To recharge 12 Volt batteries, proceed as follows:

Check fluid level in all battery cells. If necessary, add ONLY distilled water to cover separators in battery cells. Do not use tap water.

If the battery is equipped with vent caps, make sure they are installed and are tight.

If necessary, clean battery terminals.

Connect battery charge cable connector plug to panel receptacle identified by the words "12-VOLT D.C."

Connect battery charge cable clamp with red handle to the positive (+) battery terminal.

Connect battery charge cable clamp with black handle to the negative (-) battery terminal.

Start engine. Let the engine run while battery recharges. Engine idle control switch must be in off position for battery charging.

When battery has charged, shut down engine.

NOTE:

Use an automotive hydrometer to test battery state of charge and condition. Follow the hydrometer manufacturer's instructions carefully. Generally, a battery is considered to be at 100% state of charge when specific gravity of its fluid (as measured by hydrometer) is 1.260 or higher.

12

Image 14
Contents GP Series Portable Generator NOT Intended for USE in Critical Life Support ApplicationsTable of Contents Read this Manual Thoroughly Safety RulesIntroduction IntroductionFire Hazards Safety RulesExhaust & Location Hazards Electrical Shock MAY ResultStandards Index ID PlateGeneral Information AssemblyUnpacking Battery Connection Handle AssemblyHourmeter Tracks hours of operation Know the GeneratorOperation 2 120 VAC, 20 AMP, Gfci Receptacle Hourmeter1 120 VAC, 20 AMP, Duplex Receptacle 3 120 VAC, 30 AMP Receptacle 5 12 Volt DC, 10 AMP ReceptacleWattage Reference Guide HOW to USE the GeneratorConnecting Electrical Loads Grounding the GeneratorAdding Engine OIL Adding GasolineTo Start the Engine Move engine Choke knob outward to Full Choke position FigureAutomatic Idle Control Charging a BatteryStopping the Engine LOW OIL Pressure Shutdown SystemProduct Specifications Performing Scheduled MaintenanceMaintenance Schedule MaintenanceService AIR Cleaner To adjust valve clearance Adjusting Valve ClearanceClean Spark Arrestor Screen To check valve clearanceLong Term Storage Avoid spray from spark plug holes when cranking engineGeneral Other Storage TipsTroubleshooting Guide TroubleshootingPage Page Owners Warranty Responsibilities WarrantyMANUFACTURER’S Warranty Coverage PartEmission Control System Warranty Emission Related Parts MAY Include the Following if EquippedPart No H0676 Rev. D 06/07/11 Generac Power SYSTEMS, INCBOX 8 Waukesha, WI Manual del propietario Mantenimiento Guía de detección de problemas GarantíaTabla de contenidos LEA Este Manual Completamente IntroducciónReglas DE Seguridad IntroducciónPeligros DE Incendio Reglas de seguridadPeligros DEL Escape Y Ubicación ResultadoÍndice DE Estándares Placa de IDInformación general DesempaqueEnsamble Conexión DE LA Batería Instale las cubiertas de los postes de batería incluidasConozca EL Generador OperaciónMedidor DE Horas Receptáculo Gfci DE 120 VAC, 20 AMPReceptáculo DE 120 VAC, 30 AMP Receptáculo DE 12 Volt DC, 10 AMPConexión DE LAS Cargas Eléctricas Cómo Usar Este GeneradorConexión a Tierra DEL Generador Advertencia Agregar Aceite DE MotorAgregar Gasolina Arranque DEL Motor Control DE MínimoDescongelador Y Operación EN Clima Frío Detener EL MotorCarga DE LA Batería Arranque InicialRecomendaciones Generales ProgramadoPrograma DE Mantenimiento Cómo Realizar MantenimientoMantenimiento DEL Motor Mantenimiento DEL GeneradorPara Limpiar EL Generador Revisar EL Nivel DE AceiteAjuste DE LA Claridad DE LA Válvula Servicio AL Limpiador DE AireChispas Retire toda la gasolina del tanque de combustible Otros Consejos Para AlmacenamientoVástago de Tanque DE CombustibleGuía DE Detección DE Problemas Detección de fallasResponsabilidades DEL Dueño EN LA Garantía GarantíaCobertura DE LA Garantía DEL Fabricante ParteGarantía DEL Sistema DE Control DE Emisiones Programación DE Garantía Parte No H0676 Rev. D 07/06/11Manuel dentretien Fonctionnement Table des matièresLire attentivement ce manuel Guide de dépannageRemarque Lire Attentivement CE ManuelRègles DE Sécurité NE PAS faire fonctionner le générateur sous la pluieRisques Dincendie DemplacementRègles de sécurité Index DES Normes Plaque DidentificationInformations générales DéballageMontage Installer les couvercles des bornes de batterie inclus Branchement DE LA BatterieBien Connaître LE Générateur Horomètre Relève les heures de fonctionnementHoromètre Cordons ET ConnecteursFonctionnement Prise 120 V C.A., 30 aUtilisation DU Générateur Mise À LA Terre DU GénérateurAjout DE Lhuile DE Moteur Installer le générateur sur une surface de niveauAvant LE Démarrage DU Générateur Ajout DE LessenceDémarrage DU Moteur Schéma 16 Soupape darrêt12.1 Démarrage Initial Arrêt DU MoteurChargement DE LA Batterie 12.3 RedémarrageEffectuer LE Programme Dentretien Programme DE MaintenanceRecommandations Générales Caractéristiques Techniques DES ProduitsNettoyage DU Générateur Maintenance DU GénérateurMaintenance DU Moteur 4 Vérification DU Niveau DhuileRéglage DU JEU DES Soupapes Entretien DU Filtre À AIRNettoyage DE Lécran Pare Étincelles Autres Conseils DE Stockage GénéralitésStockage À Long Terme Ne pas stocker lessence dune saison sur lautreGuide DE Dépannage DépannageResponsabilités DE Garantie DU Propriétaire GarantieCouverture DE Garantie DU Fabricant 1ère partieGarantie DU Système DE Contrôle DES Emissions 2ème partieProgramme DE Garantie Référence 0H0676 Rév. D 07/06/11

005735-0, 005734-0 specifications

Generac 005735-0 and 005734-0 are high-performance energy solutions designed for residential and light commercial use, offering reliable power backup in various situations. Each model boasts distinct features and technologies that set them apart in the energy market.

The Generac 005735-0 is a 22 kW air-cooled automatic standby generator, engineered to deliver robust performance in the face of power outages. It is especially prized for its advanced Quiet-Test mode, which allows the generator to run at a lower speed for a five- or twelve-minute test, significantly reducing noise levels during routine checks. This feature makes it an excellent choice for neighborhoods with noise restrictions.

Designed with durability in mind, the 005735-0 utilizes a corrosion-resistant aluminum enclosure, ensuring longevity even in harsh weather conditions. Equipped with Generac's G-Flex technology, this model can operate efficiently while providing a steady power supply to essential appliances and systems like HVAC, refrigerators, and lights.

On the other hand, the Generac 005734-0 model features similar specifications but may serve a different market need with slight variations in design. Often marketed for slightly lower power requirements, this model provides a dependable 18 kW output.

Both generators incorporate a robust mobile link monitoring capability, allowing users to check the status and statistics of their generator remotely via a smartphone app. This feature adds a layer of convenience and peace of mind, allowing homeowners to monitor their systems from anywhere.

In terms of installation, these models are straightforward to set up, compatible with existing natural gas or liquid propane systems. They are also supported by Generac's extensive network of authorized installers, making the purchasing and installation process seamless for consumers.

Furthermore, both models come with a five-year limited warranty, affirming Generac's confidence in their reliability and durability. With the ability to provide instant power restoration during outages, the Generac 005735-0 and 005734-0 are ideal options for those prioritizing convenience and peace of mind in their homes.

Overall, these generators embody Generac's commitment to quality, innovation, and user-friendly technology, making them trusted choices for backup power solutions.