Section 5 — Troubleshooting

Centurion Liquid-cooled 15 kW and 25 kW Generators

5.1TROUBLESHOOTING POINTS

PROBLEM

CAUSE

CORRECTION

Engine won’t crank.

1.

15 amp fuse blown.

1.

Replace fuse.

 

2.

Loose or corroded or defective

2.

Tighten, clean or replace

 

 

battery cables.

 

battery cables as necessary.

 

3.

Defective starter contactor.

3.

Replace contactor.

 

4.

Defective starter motor.

4.

Replace starter motor.

 

5.

Dead or Defective Battery.

5.

Remove, change or replace battery.

Engine cranks but won't start

1.

Out of fuel.

1.

Replenish fuel.

 

2.

Fuel solenoid (FS) is defective

2.

Replace solenoid.

 

3.

Open Wire #14 from Engine Control

3.

Reconnect wire.

 

 

circuit board.

 

 

 

4.

Spark plugs defective.

4.

Clean, regap or replace plugs.

Engine starts hard, runs rough.

1.

Flame arrestor (air cleaner) plugged or

1.

Clean or replace as needed.

 

 

damaged.

 

 

 

2.

Plugged fuel line.

2.

Unclog fuel line.

 

3.

Defective spark plugs.

3.

Clean, regap or replace plugs.

Engine starts then shuts down.

1.

Engine oil level is low.

1.

Check oil and add oil as needed.

 

2.

Engine is overheated.

2.

Check cooling system for leaks.

 

3.

Defective Low Oil Pressure Switch

3.

Replace switch.

 

4.

Defective Coolant Temperature Switch

4.

Replace switch.

 

5.

Defective Control Module circuit board.

5.

Replace board.

 

6.

Coolant Level is Low.

6.

Repair leak - Add coolant.

 

7.

Defective Low Coolant Level Switch

7.

Replace Switch.

AUTO/OFF/MANUAL Switch at

1. Defective Auto/Off/Manual switch

1.

Replace switch.

OFF, engine continues to run

2. Open/disconnected wire #15A between

2.

Reconnect/close wire.

 

 

Auto/Off/Manual switch and Control

 

 

 

 

Module circuit board.

 

 

 

3.

Defective Control Module circuit board

3.

Replace board.

No AC output from generator.

1. Check main line circuit breaker.

1.

Reset to ON or CLOSED.

 

2.

Check circuit breaker & fuses.

2.

Reset and replace, if necessary.

 

3.

Transfer switch set to NORMAL position

3.

Set to GENERATOR position.

 

4.

Generator internal failure.

4.

Contact an Authorized Generac

 

 

 

 

facility.

 

5.

Thermal circuit breaker open.

5.

Auto-reset - Wait 5 min. and

 

 

 

 

attempt restart.

Generac® Power Systems, Inc. 23

Image 25
Contents Centurion ‹ Operation and Maintenance Authorized Service Dealer Location‹ HOW to Obtain Service IntroductionInside Front Cover General Hazards Electrical Hazards Generator Transfer SwitchAutomatic System Operation Generator AC Connection Systems‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.1 LOW OIL Pressure SwitchMain Circuit Breaker Generator Fuel SystemLifting the Generator UnpackingReconfiguring the Fuel System SpecificationsFuel Consumption ‹ 1.10.1 GeneratorBefore Installation Torque SpecificationsGenerator Installation Engine OIL RecommendationsGenerator Mounting Support Generator LocationBasic Standby Electric System ‹ 2.1.1 Nfpa StandardsEmergency Circuit Isolation Method Total Circuit Isolation MethodGrounding the Generator Battery Installation Transfer Switch Start Signal ConnectionsGenerator AC Neutral Connections ‹ 2.10.1 Vented BatteriesPreparation Before START-UP ‹ 3.2.2 AUTO/OFF/MANUAL Switch Using a Standard GTS Transfer Switch‹ 3.2.3 Fault Indicator Lamp Control Console ComponentsManual Transfer START-UP Automatic Operation ‹ 3.2.6 SET Exercise Time SwitchWeekly Exercise Cycle Engine Block HeaterOverload Protection for Engine DC Electrical System Cooling SystemChecking Fluid Levels ‹ 4.5.2 Check Battery ‹ 4.4.2 Battery Fluid‹ 4.5.4 Inspect Cooling System ‹ 4.5.5 Perform Visual Inspection‹ 4.5.10 Changing the Engine AIR Cleaner Miscellaneous Maintenance‹ 4.6.1 Cleaning the Generator ‹ 4.5.11 Spark Plugs‹ 4.6.3 Battery Maintenance ‹ 4.6.2 Battery‹ 4.6.4 Battery Replacement ‹ 4.6.5 Rodent Protection‹ 4.7.1 Removal from Service OUT of Service Procedure‹ 4.7.2 Return to Service Fuel Pipe SizingService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsCenturion Liquid-cooled 15 kW and 25 kW Generators Installation Diagram Section DC-VR Customer Connection 120/240V 1-PHASE To Control Panel Terminal Strip Connector Interface Assembly Housing Governor ConnectorCover Connector Housing ASM Motor StepperWasher Shakeproof EXT 5/16 STL BASE,MOUNTING 1.5L STNRD&ACSTCDampener Vibration Washer Flat 5/16 ZincWeld Stud Under Roof GRD Wire Assy 99HSB Assembly BASE-DOOR Ground WireAssembly Cover Access Roof ACSTC&STND Cmprtmnt 1.5LPanel for Access Cover Cable Door Weldment 1.5 EPS Roof Acstc & Stnd Cmprtmnt 1.5LWasher Self Locking Dome Baffle Cntrl PNL 1.5L AcousticTo a Silksc Wire AssemblyHourmeter Holder FuseHardware ARM Adjust Alternator Switch OIL PressureGround Wire Starter ENGINE-1.5L16 7 Radiator 1.5L Tank Coolant RecoveryVenturi 1.5L Modine Guard FAN 1.5L ModineVapor Gasket AIR Cleaner Adapter Cover AIR CleanerWeldment Mounting Base Flange Fuel InletTo Engine Crankshaft Assy Rotor 10KW Housing BlowerAssy Rotor 15KW Assy Rotor 20KWBOOT, Battery Cable ASSY,WIRE#16 REDBRACKET, Battery Hold Down Battery Post Cover RED+Nipple TOE 1.5NPTX5.5 BLK Iron Manifold Exhaust 1.5LSaddle 2 Inch PIPE,EXHAUST 1.5L STNDRD&ACSTCMANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule