Briggs & Stratton 30000 SERIES system manual No leakage is permitted

Page 11

Install the flexible, gaseous hose (supplied) between the home generator Fuel Inlet port and rigid piping to prevent thermal expansion or contraction from causing excessive stress on the piping material.

NOTE: Where local conditions include earthquake, tornado, unstable ground, or flood hazards, special consideration shall be given to increase strength and flexibility of piping supports and connections.

caution

The supplied flexible gaseous pipe is not to be installed underground or in contact with the ground.

The entire flexible gaseous pipe must be visible for periodic inspection and must not be concealed within, contact, or run through any wall, floor, or partition.

Piping must be of the correct size to maintain the required supply pressures and volume flow under varying generator load conditions with all gas appliances connected to the fuel system turned on and operating.

Use a pipe sealant or joint compound approved for use with NG/LPG on all threaded fittings to reduce the possibility of leakage.

Installed piping must be properly purged and leak tested, in accordance with applicable codes and standards.

warning

Propane and Natural Gas are extremely flammable and explosive.

Fire or explosion can cause severe burns or death.

Before placing the home generator into service, the fuel system lines must be properly purged and leak tested.

No leakage is permitted.

Consider the following factors when planning to install the fuel supply system:

A minimum of one accessible, approved manual shutoff valve shall be installed in the fuel supply line within

6 ft (1.8 m) of the home generator. A union or flanged connection shall be provided downstream from this valve to permit removal of controls.

LP gas fuel supply pressure should be 7 to 11 inches of water (in. W.C.) at full load with all gas appliances turned on and operating.

Natural gas fuel supply pressure at the generator’s fuel inlet port should be between 7 to 11 inches of water (in. W.C.) at full load with all gas appliances turned on and operating.

The home generator unit has been factory set to run on natural gas. The unit can be converted from natural gas to LP gas or vice versa using two people and special tools. See Fuel Conversion, later in this manual.

It is recommended that the fuel connection incorporate the following components:

A minimum 10 ft. (3 m) section of gas pipe between the primary fuel regulator and the generator fuel inlet connection (acts as accumulator for high block loads).

A manual fuel shut-off valve located in the interior of the building.

A manual fuel shut-off valve located outside the building, just before the generator unit.

Where the formation of hydrates or ice is known to occur, piping should be protected against freezing. The termination of hard piping should include a sediment trap where condensate is not likely to freeze.

A manometer port should be provided.

The manometer port permits temporary installation of a manometer to ensure that the engine receives the correct fuel pressure to operate efficiently throughout its operating range.

NOTE: A digital manometer, P/N 19495, is available at your Briggs & Stratton service center.

11

Image 11
Contents Series Liquid-Cooled Home Generator System Model Number Model Revision Serial Number Where to Find UsDate of Purchase Generator EngineTable of Contents BRIGGSandSTRATTON.COM Safety RulesHazard Symbols and Meanings Page Never operate generator without protective housing or covers Installation General Location Guidelines Home Generator LocationGenerator Location Female NPT Electrical and Fuel Inlet LocationsLifting the Generator Concrete SlabGaseous Fuel System Access DoorsTo Open an Access Door To Close an Access DoorNo leakage is permitted LP Vapor Natural Fuel ConsumptionNatural Gas LP Vapor +12 Volt DC, .5 Amp Output Internal auxiliary power supply System ConnectorsPole Connector Plug Grounding the Generator Fault Detection SystemTo install the remote LED indicator Generator AC Connection SystemSystem Control Panel Final Installation ConsiderationsFuel Conversion BatteryFuel Supply System Initial Start-up No LoadVoltage Phi Lamda Schematic/ Wiring Diagram Operation Setting Exercise TimerInstallation Inspection ControlsBRIGGSandSTRATTON.COM Manual de Instalación y Arranque Número de Modelo Revisión Número de Serie Dónde encontrarnosFecha de compra Generador MotorMandos Utilización Instrucciones importantes de seguridad InstalaciónSímbolos de Peligro y Significados Conserve estas instruccionesAte para arriba el pelo largo y quite la joyería Tensión peligrosaNo modifique al generador en ninguna forma PrecauciónInstalación Pautas Generales para la Ubicación del Generador Ubicación del Sistema de Generador de DomésticoUbicación del Generador Elevación del Generador Solera de concretoUbicación de las entradas eléctricas y de combustible Para cerrar una puerta de acceso Puertas de AccesoPara abrir una puerta de acceso No encienda un cigarrillo o fume Sistema de combustible gaseosoVapor de Gas Dimensiones de la Cañería de CombustibleConsumo de Combustible Gas Natural Vapor de PLCableado para toma de 10 polos Conexiones de SistemaSistema de Detección de Fallas Sistema de Conexión de c.a. del GeneradorConexión a Tierra del Generador Interconexiones del Circuito de ControlConsideraciones finales para la instalación Panel de Control del SistemaNota no utilice una batería de ciclo profundo Sistema de Suministro de CombustibleArranque inicial sin carga BateríaTensión Phi Lamda Conversión de combustibleSecuencia de operación automática MandosUtilización Temporizador de enfriamiento del motor Configuración del temporizador de prácticaInspección posterior a la instalación BRIGGSandSTRATTON.COM Manuel d’Installation et Démarrage Numéro de modèle Révision Numéro de série Où nous trouverDate d’achat Génératrice MoteurCommandes Fonctionnement Directives de sécurité importantes InstallationSécurité Symboles de Danger et MoyensDirectives de sécurité importantes Tension dangereuse Avis Précautions Lors du Déballage Responsabilités de l’InstallateurDescription de l’équipement Responsabilités de l’AcheteurDégagement Autour de la Génératrice Emplacement du Génératrice d’état d’AttenteDirectives Générales Concernant l’Emplacement Installez l’unité à l’extérieur SeulementSoulèvement de la Génératrice Dalle de bétonPour fermer une porte d’accès Instalación CommandesPortes d’Accès Pour ouvrir une porte d’accèsAucune fuite ne peut être tolérée Le système de combustible gazeuxGrosseur du Tuyau de Combustible Consommation de CombustibleGas Naturel Vapeur PL Propane GazEntretien Dépannage Garantie Connexions de systèmeSystème de Détection des Pannes Interconnexions du Circuit de CommandeSécurité Instalación Commandes Mise à la Masse de la GénératriceFusible de 15 Ampères Tableau de Commande du SystèmeConsidérations pour l’installation finale Huile à Moteur Interrupteur de systèmeDémarrage initial sans charge Système de refroidissementBatterie Système d’Alimentation en CombustibleLamda Conversion du combustibleTension Tout en observant l’afficheur de l’analyseur d’oxygèneSéquence de fonctionnement automatique CommandesCapteur de Prise en Charge de la Tension de Service FonctionnementRéglage de la minuterie de cycle d’exercice Vérification installationThis page reserved